Page 1
6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide...
Page 3
6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide...
Page 4
Note Before using this information and the product it supports, read the general information in the Notices section; and read the Safety Information and the Environmental Notices and User Guide on the Lenovo Documentation CD that came with your product.
This section contains information for trained service technicians. Inspecting for unsafe conditions Use this information to help you identify potential unsafe conditions in a Lenovo product that you are working on. Each Lenovo product, as it was designed and manufactured, has required safety items to protect users and service technicians from injury.
Make sure that the insulation is not frayed or worn. 4. Remove the cover. 5. Check for any obvious non-Lenovo alterations. Use good judgment as to the safety of any non-Lenovo alterations. 6. Check inside the system for any obvious unsafe conditions, such as metal filings, contamination, water or other liquid, or signs of fire or smoke damage.
v Never assume that power has been disconnected from a circuit. Check it to make sure that it has been disconnected. v If you have to work on equipment that has exposed electrical circuits, observe the following precautions: – Make sure that another person who is familiar with the power-off controls is near you and is available to turn off the power if necessary.
Page 11
L001 DANGER Hazardous voltage, current, or energy levels are present inside any component that has this label attached. Do not open any cover or barrier that contains this label. (L001) Safety...
Page 12
Electrical voltage and current from power, telephone, and communication cables are hazardous. To avoid a shock hazard: v If Lenovo supplied a power cord(s), connect power to this unit only with the Lenovo-provided power cord. Do not use the Lenovo-provided power cord for any other product.
Page 13
Exchange only with the Lenovo-approved part. Recycle or discard the battery as instructed by local regulations. In the United States, Lenovo has a process for the collection of this battery. For information, call 1-800-426-4333. Have the Lenovo part number for the battery unit available when you call.
Page 14
C022 CAUTION: This product might be equipped with a hard-wired power cable. Ensure that a licensed electrician performs the installation per the national electrical code. (C022) Installation and User's Guide...
Page 15
R001 Important: The following general safety information should be used for all rack-mounted devices: DANGER Observe the following precautions when working on or around your IT rack system: v Heavy equipment—personal injury or equipment damage might result if mishandled. v Always lower the leveling pads on the rack cabinet. v Always install stabilizer brackets on the rack cabinet.
CAUTION: v Do not install a unit in a rack where the internal rack ambient temperatures will exceed the manufacturer’s recommended ambient temperature for all your rack-mounted devices. v Do not install a unit in a rack where the air flow is compromised. Ensure that air flow is not blocked or reduced on any side, front, or back of a unit used for air flow through the unit.
Page 17
The upstream circuit breaker for Normal AC and Bypass AC must be easily accessible. The unit can be disconnected from AC power source by opening this circuit breaker. This circuit breaker is used for backfeed protection and must comply with IEC/EN 62040-1 (the creepage and clearance distances shall meet the basic insulation requirements for pollution degree 2).
Before installing your equipment, read the safety instructions. Then, follow the instructions in this manual for setting up and using the product. To discover the entire range of Lenovo products and the options available for the Lenovo UPS device, we invite you to visit our website or contact your Lenovo representative.
CD. End of life Lenovo will process products at the end of their service life in compliance with local regulations. Lenovo works with companies in charge of collecting and eliminating our products at the end of their service life.
Page 21
The battery pack can be removed to comply with regulations and in view of correct disposal. With the Lenovo UPS device, you can eliminate the effects of power disturbances and guard the integrity of your equipment. Providing outstanding performance and reliability, the Lenovo UPS device's unique benefits include: v True online double-conversion technology with high power density, utility frequency independence, and power generator compatibility.
The kit is available from Lenovo. Refer to the instructions in the kit to install the brackets properly. The brackets are not required when the UPS and EBMs are installed in a pre-positioned rack.
Connectors for battery modules (to the UPS or to the other battery modules) Connectors for automatic recognition of battery modules (UPS-to-EBM or EBM-to-EBM) Battery circuit breaker Figure 3. 5594-9BX Extended Battery Module Control panel The UPS has a five-button graphical LCD front panel. It provides useful information about the UPS itself, load status, events, measurements, and settings.
Indicator Status Description The UPS has an active alarm or fault. See Chapter 8, “Troubleshooting,” on page 55 for additional information. LCD description After 5 minutes of inactivity, the LCD displays the screen saver. The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen.
Is Battery Operation Being status Cause Description Charged? End of The UPS is in Battery mode This warning is backup time and the battery packs are approximate, and the actual running low. time to shut down might vary significantly. Depending on the UPS load and number of Extended Battery Modules (EBMs), the 1 beep every...
[Part/Serial number] / [UPS/NMC firmware] / [Com card IPv4], [Com card IPv6], [Com card MAC] / [Detected accessories] Register product Link to Lenovo website User settings The following table displays the options that can be changed by the user. Submenu Available settings...
Page 29
Submenu Available settings Default settings In/Out settings Output voltage [200V] [208V] [220V] [230V] [230V] [240V] [250V] Can be changed only in Standby mode Output frequency [Disabled] Frequency converter: [Enabled] [Disabled] Frequency settable in frequency converter mode Output mode [Industrial] [Network] [Network] Set UPS behavior regarding transfer on...
Page 30
Submenu Available settings Default settings On/Off settings Cold start [Enabled] [Disabled] [Enabled] Authorize the product to start on battery power. Forced reboot [Enabled] [Disabled] [Enabled] If utility power recovers during a shutdown sequence: If Enabled, the shutdown sequence will complete and wait 10 seconds prior to restart.
Page 31
Submenu Available settings Default settings On/Off settings Sleep mode [Enabled] [Disabled] [Enabled] (continued) If Disabled, LCD and communication will turn OFF immediately after UPS is OFF. If Enabled, LCD and communication stays ON 90 minutes after UPS is OFF. Remote command [Enabled] [Disabled] [Enabled] If Enabled, shutdown...
HotSwap MBP The HotSwap MBP allows you to service or replace the UPS without interrupting the connected loads. Standard installations for the HotSwap MBP Rack installation In a rack configuration, the MBP should always be mounted behind the extended battery module(s) -- not behind the UPS. Figure 4.
Page 34
v UPS supply: Green light; when active, the UPS output is available, and the Bypass switch can safely be turned to UPS position v Bypass mode: Red light; when active, indicates that the HotSwap MBP is in Bypass mode (Bypass switch turned to Bypass position) Normal AC source switch and Bypass AC source switch: Use to switch off the AC source for the UPS (for UPS maintenance and replacing) MBP status detection: A signal cable, with RJ11 connector to plug to the UPS,...
Note: Packing materials must be disposed of in compliance with all local regulations concerning waste. Recycling symbols are printed on Lenovo the packing materials to facilitate sorting. Checking the accessory kit: UPS Procedure v Verify that the following additional items are included with the UPS:...
Battery power cable, with attached battery detection cable Stabilizer bracket (4 screws included) Rack kit for 19-inch enclosures Note: Disregard the EBM installation instructions if you are installing the EBM with a new UPS at the same time. Use the UPS instructions to install both the UPS and the EBM.
Page 38
Figure 9. 8/11k VA 1Phase MBP I/O cover MBP I/O "UPS connection" cover (2) conduits with internal wires for UPS Input/Output connection (4) conduit fittings Fixation kit for MBP I/O covers (including screws) Rack kit for 19-inch enclosures Fixation kit for Rack mounting (including square nuts and screws) Tower and wall mounting kit (including 2 ears and screws) Figure 10.
Rack kit for 19-inch enclosures -- including square nuts and screws ( Tower and Wall mounting kit (including 2 ears and screws) Mechanical mounting For rack installations, mount the MBP to the rail behind an EBM, just below the UPS. For tower installations, mount the MBP to an EBM. Connecting the EBM(s) About this task Note: A small amount of arcing might occur when connecting EBMs.
3. Remove the three screws to pull out the metal protection cover of the battery pack. 4. Pull out the plastic handle of the left and right battery packs, and slide the packs out slowly on to a flat and stable surface. Use two hands to support the battery packs.
The rails and necessary hardware are supplied by IBM (optional). Tower installation About this task To install the unit in a tower configuration: Procedure 1. Place the UPS on a flat, stable surface in its final location. 2. Always keep 150 mm of free space behind the UPS rear panel. 3.
4. Adjust the orientation of the LCD panel and the logo, as shown. 5. Adjust the angle of vision of the LCD panel., as shown. Installing the communication card About this task Follow these steps to install the UPS Network Management Card if it is not preinstalled.
Procedure 1. Remove the connector panel blank ( ), which is secured by two screws. 2. Insert the UPS Network Management Card into the slot. Secure the panel by tightening the two screws. Installation requirements Recommended protective devices and cable cross-sections 1.
Table 2. Recommended cable cross-sections Terminal wire size Terminal rating Minimum wire size Tightening torque 4-25 mm / 12-4 AWG 10 mm / 8 AWG 2.03 Nm / 18 in-lb 105°C 16 mm / 6 AWG 90°C Copper wire, solid or stranded. Installation depending on the system earthing arrangement (SEA) UPS with common Normal and Bypass AC inputs Installation and User's Guide...
Common input sources connection (1Phase units) About this task 1. Make sure the jumper is connected. 2. Insert the Normal AC cable through the cable gland. 3. Connect the three cables to the Normal AC source terminal blocks. 4. Insert the Output cable through the cable gland.
Separate input source connection (1Phase units) About this task 1. Remove the jumper. 2. Insert the Normal AC cable through the cable gland. 3. Connect the three cables to the Normal AC source terminal blocks. 4. Insert the Bypass AC cable through the cable gland.
Always connect the ground wire first. 1. Remove the jumper. 2. Insert the Normal AC cable through the cable gland. 3. Connect the three cables to the Normal AC source terminal blocks. Do not connect anything to the Bypass terminal blocks.
8/11k VA 1Phase Procedure 1. Remove the top cover of the MBP I/O UPS connection cover after removing the 3 screws. 2. Punch the knockouts of the MBP I/O UPS connection cover and insert the 2 provided conduit fittings inside. 3.
Page 50
10. Punch the Input and Output knockouts of the UPS I/O terminal block (TB) cover and insert the 2 provided conduit fittings inside. 11. Insert the conduits through the previously mounted conduit fittings of the UPS I/O TB cover, following color coding on the conduits and the UPS I/O TB cover: blue for UPS Input;...
8/11k VA 3Phase with common Normal and Bypass AC source Procedure 1. Connect the two integrated power cables to the UPS I/O terminal blocks, following color coding on the cables and the UPS I/O cover: blue for UPS Input; red for UPS Output. Chapter 4.
2. Connect the MBP detection cable to the specific UPS connector. 3. Slide the MBP I/O cover after removing the 5 screws, to access to MBP terminal blocks. 4. Insert the Normal AC source cable through the cable gland. 5. Connect the wires to the Normal AC source (Input) terminal blocks (do not remove the Input Bypass AC jumper and the UPS Input Bypass jumper inside the UPS I/O cover.
Page 53
3. Insert a power cable (refer to Table 2 on page 26 for cable cross-section) through the cable gland of the MBP Bypass Input cover . (The cable is not provided in the packaging). 4. Connect the wires to the Input BP terminal blocks of the MBP Bypass Input cover 5.
Page 54
10. Remove the Input Bypass AC jumper 11. Punch the Bypass AC Source knockout of the MBP I/O cover and insert a provided cable gland inside. 12. Insert the Normal AC source cable through the cable gland. 13. Connect the wires to the Normal AC source (Input) terminal blocks. 14.
Procedure 1. Press the power ( ) button on the UPS front panel until the UPS front panel display illuminates and shows a status of "UPS starting...". The UPS cycles through Standby mode to Battery mode. The indicator illuminates solid. The UPS supplies power to your equipment using batteries. 2.
13. Check that the UPS is in Online mode by checking its display panel. The load is now protected by the UPS. Monitoring the UPS operating mode The Lenovo UPS front panel indicates the UPS status through the UPS indicators. See “Control panel” on page 7. Operating modes: descriptions...
Depending on overload conditions, the UPS remains in Bypass mode for at least 5 seconds and will stay in this mode if three transfers to Bypass occur within 20 minutes. The UPS transfers to Bypass mode when: v the user activates Bypass mode through the front panel v the UPS detects an internal failure v the UPS has an overtemperature condition v the UPS has an overload condition listed in the Specifications section...
Transferring the UPS between modes From Online or Battery to Bypass mode. Press any button to activate the menu options, then select Control and Go to Bypass. From Bypass to Online or Battery mode. Press any button to activate the menu options, then select Control and Go back normal.
Configuring battery settings Automatic battery test Automatic battery tests are done every week in automatic charging mode and at each cycle in Advanced Battery Management (ABM) mode. The frequency of the tests can be modified using the LCD panel: see "Automatic battery test" in “User settings”...
RS232 or USB communication port on the UPS. Results The UPS can now communicate with Lenovo power management software. Relay output contacts The UPS incorporates four relay outputs; each one is available with a normally closed or open contact. Status active information: (if contact between...
Important: The relay output contacts must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of 250 Vac/5A. Remote On/Off Remote On/Off allows remote control of the power ( ) button to switch the UPS on and off.
RPO connections: Normally closed Normally open Terminal wire size rating is 0.32-4 mm (22-12 AWG). Remote control connection and test 1. Ensure that the UPS is shut down and the utility power is disconnected. 2. Remove the RPO connector from the UPS by loosening the screws. 3.
the communication bay. Replacing the communication card About this task Follow these steps to replace the UPS Network Management Card. Procedure 1. Turn off the UPS. 2. Disconnect the network cable. 3. Remove the connector panel blank ( ), which is secured by two screws. 4.
Note: DO NOT DISCONNECT a battery pack while the UPS is in Battery mode. Be aware that the UPS can switch to Battery mode at any time and without warning. Consider all warnings, cautions, and notes before replacingbattery packs. Important: v Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions.
Page 67
To replace the battery pack: Procedure 1. Remove the center section of the front bezel. 2. Remove the four captive screws to open the front bezel. 3. Remove the three screws to pull out the metal protective cover of the battery pack.
Replacing the EBM(s) About this task CAUTION: The weight of this part or unit is more than 55 kg (121.2 lb). It takes specially trained persons, a lifting device, or both to safely lift this part or unit. (C011) To replace the EBM(s): Procedure 1.
During the battery test, the UPS transfers to Battery mode and discharges the battery pack for 25 seconds. The front panel displays "Battery test in progress" and the percentage of the test completed. Replacing the UPS The HotSwap MBP allows you to service or replace the UPS without interrupting the connected loads.
Figure 12. Locking the UPS Input switch and UPS Bypass Input switch (8/11k VA 3Phase) 6. Wait 30 seconds for the UPS to stop functioning. Check the UPS display panel to verify that the UPS is not functional. 7. Remove the access cover on the terminal block cover and use a voltmeter to ensure that hazardous voltage is no longer present.
Recycling the used equipment Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment. Refer to the Lenovo Systems Environmental Notices and User Guide on the Lenovo Documentation CD for more information. Important:...
Page 72
v Do not dispose of batteries in a fire or expose them to temperatures higher than 100°C (212°F). Battery packs might explode. v Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes. It can be toxic. v Dispose of the battery as required by local ordinances or regulations.
Chapter 8. Troubleshooting The Lenovo UPS is designed for durable, automatic operation. It will alert you whenever operating problems occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
Page 74
Conditions Possible cause Action The UPS has been in Battery Battery low Shut down equipment. mode too long. This warning is approximate, and the actual time to shut down might vary significantly. Depending on the UPS load and LED is On. the number of Extended Battery Modules (EBMs), the "Battery 1 beep every 3...
Page 75
Conditions Possible cause Action Power overload Power requirements exceed the Remove some of the equipment UPS capacity (greater than 100% from the UPS. of nominal; see “UPS The UPS continues to operate, specifications” on page 61 for but it might switch to Bypass specific output overload ranges).
Conditions Possible cause Action MBP disconnected The HotSwap MBP is not If the HotSwap MBP is detected. connected to the UPS, check that the detection connector is correctly plugged. Silencing the alarm Procedure 1. Press the ESC (Escape) button on the front panel display to silence the alarm. 2.
Structural parts: Purchase and replacement of structural parts (components such as the top cover) is your responsibility. If Lenovo acquires or installs a structural part at your request, you will be charged for the installation.
Page 78
Table 5. Parts listing table: Extended battery module (continued) Description Type Part No. 55949BX EBM Power Cord 6 Feet 240V Tier 1 CRU 00FP795 4 Post Rail Kit Tier 2 CRU 00FP796 9PX 8/11K UPS Battery Module Spare Tier 2 CRU 00FP798 Tower pedestal feet Tier 1 CRU...
Appendix A. Specifications UPS specifications The Lenovo 6U Rack or Tower UPS, model 5594-8KX and model 5594-9KX, is a 1-phase UPS unit. The 6U Rack or Tower UPS, model 5594-8PX and model 5594-9PX, is a 3-phase UPS unit with a wye connected load between 380V and 415V.
Page 80
Table 10. Electrical input connections Model Input connection Input cable 55594-8PX, 5594-8KX Hardwired Not provided 5594-9PX, 5594-9KX Table 11. Electrical output All models Normal mode Battery mode Voltage regulation ±1% ±1% Efficiency > 91% > 98% (High Efficiency mode) > 94.5% for 8-11kVA models Frequency Sync with line ±5% of nominal line ±0.5% of auto-selected...
Page 81
Table 13. AC input and output (1Phase models) 5594-8KX 5594-9KX AC Input power 200-240VAC, 50/60Hz, 1ph, 200-240VAC, 50/60Hz, 1ph, 40A max 50A max AC Output power 50/60Hz, 1ph; 50/60Hz, 1ph; 200VAC, 8000VA, 7200W, 200VAC, 10000VA, 9000W, 40.0A; 50.0A; 208VAC, 8000VA, 7200W, 208VAC, 10000VA, 9000W, 38.5A;...
Page 82
Table 15. Weights and dimensions (Power Module) (continued) Model (Power Dimensions D x W x H (mm / Module) inch) Weight (lb / kg) 8K Power Module 700 x 440 x 130 (27.6 x 17.3 x 5.1) 42 / 19 (KX) 11K Power Module 700 x 440 x 130 (27.6 x 17.3 x 5.1)
Table 17. Environmental and safety standards (continued) Storage temperature 0 to 40°C (32 to 104°F) with batteries -15 to 60°C (5 to 140°F) without batteries Transit temperature -25 to 55°C (-13 to 130°F) Relative humidity 0 to 95% no condensing Operating altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m...
Page 84
8/11k VA 1Phase MBP11Ki 8/11k VA 3Phase Terminal Blocks Output (4) C19 + Terminal blocks Overall dimensions D x W x H 6.8 x 13.2 x 5.1 in. / 172 x 336 x 130 mm Minimum rack depth for UPS with MBP: 900mm (35.4 inches) Weight (lb / kg) 13.7 / 6.2 12.1 / 5.5...
Page 85
Recommended upstream protection (normal upstream source) UPS power rating Upstream circuit breaker 8000VA D curve - 50A 11000VA D curve - 70A Recommended upstream protection (bypass AC source) UPS power rating Upstream circuit breaker 8000VA D curve - 50A 11000VA D curve - 70A Appendix A.
Lenovo to assist you. Use this information to obtain additional information about Lenovo and Lenovo products, and determine what to do if you experience a problem with your Lenovo system or optional device. Note: This section includes references to IBM web sites and information about obtaining service.
The troubleshooting information or the diagnostic programs might tell you that you need additional or updated device drivers or other software. Lenovo maintains pages on the World Wide Web where you can get the latest technical information and download device drivers and updates.
In the U.S. and Canada, call 1-800-IBM-SERV (1-800-426-7378). Hardware service and support IBM is Lenovo's preferred service provider for the System x, Flex System and NeXtScale System products. You can receive hardware service through your Lenovo reseller or from IBM. To locate a reseller authorized by Lenovo to provide warranty service, go to http://www.ibm.com/partnerworld and click Business Partner Locator.
Page 90
IBM Taiwan Corporation 3F, No 7, Song Ren Rd. Taipei, Taiwan Telephone: 0800-016-888 Installation and User's Guide...
(TBW). A device that has exceeded this limit might fail to respond to system-generated commands or might be incapable of being written to. Lenovo is not responsible for replacement of a device that has exceeded its maximum guaranteed number of program/erase cycles, as documented in the Official Published Specifications for the device.
Lenovo makes no representations or warranties with respect to non-Lenovo products. Support (if any) for the non-Lenovo products is provided by the third party, not Lenovo. Some software might differ from its retail version (if available) and might not include user manuals or all program functionality.
Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. Lenovo is not responsible for any radio or television interference caused by using other than recommended cables and connectors or by unauthorized changes or modifications to this equipment.
Page 95
EU-Mitgliedsstaaten und hält die Grenzwerte der EN 55022 Klasse A ein. Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu installieren und zu betreiben. Des Weiteren dürfen auch nur von der Lenovo empfohlene Kabel angeschlossen werden. Lenovo übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen, wenn das Produkt ohne Zustimmung...
Page 96
Konformitätserklärung nach Paragraf 5 des EMVG ist die Lenovo (Deutschland) GmbH, Gropiusplatz 10, D-70563 Stuttgart. Informationen in Hinsicht EMVG Paragraf 4 Abs. (1) 4: Das Gerät erfüllt die Schutzanforderungen nach EN 55024 und EN 55022 Klasse A. Nach der EN 55022: „Dies ist eine Einrichtung der Klasse A. Diese Einrichtung kann im Wohnbereich Funkstörungen verursachen;...
Page 97
Korea Communications Commission (KCC) statement This is electromagnetic wave compatibility equipment for business (Type A). Sellers and users need to pay attention to it. This is for any areas other than home. Russia Electromagnetic Interference (EMI) Class A statement People's Republic of China Class A electronic emission statement Taiwan Class A compliance statement Appendix C.
Advanced Battery Management (ABM) A three-stage charging system designed to prolong the service life of Lenovo UPS batteries. By charging the batteries only when necessary, battery life is significantly improved. Charging stage one: quickly recharges battery to approximately 90% of capacity. Charging stage two: fully charges the battery to 100%.
Need help?
Do you have a question about the RT8.0kVA and is the answer not in the manual?
Questions and answers