Revision:A • RoHS PARTS LIST has been added. Revision:B • MUH-GA50VB- has been added. TECHNICAL CHANGES MUH-A18WV - MUH-GA50VB - 1. Oil separator has been removed. 2. Model name has been changed. Indication of capacity has been changed. (BTU kW) MUH-A24WV - MUH-GA60VB - MUH-A30WV -...
Page 3
New Specification Current Specification The incompatible refrigeration oil easily separates from Since refrigerant and refrigeration oil are compatible each, refrigerant and is in the upper layer inside the suction muffler. refrigeration oil backs to the compressor through the lower Raising position of the oil back hole enables to back the position oil back hole.
Page 4
2.Refrigerant piping 1 Specifications Use the refrigerant pipes that meet the following specifications. Outside diameter Wall Pipe Insulation material thickness 0.8 mm 6.35 For liquid Heat resisting foam plastic 0.8 mm 9.52 0.8 mm Specific gravity 0.045 Thickness 8 mm 12.7 For gas 1.0 mm...
PART NAMES AND FUNCTIONS MUH-GA50VB MUH-GA60VB MUH-GA80VB Air inlet Air inlet (back and side) (back and side) Piping Drainage hose Air outlet Air outlet Drain outlet ACCESSORIES MUH-GA60VB MUH-GA50VB MUH-GA80VB Drain socket Drain cap {33 Drain cap {16 —...
SPECIFICATION Outdoor model MUH-GA50VB MUH-GA60VB Cooling Heating Cooling Heating Function Single phase Single phase Power supply 230V, 50Hz 230V, 50Hz Capacity Dehumidification — — Air flow(High) 2,196 2,760 K /h Power outlet Running current 7.93 7.23 10.39 10.70 Power input 1,720 1,550 2,350...
Page 7
Outdoor model MUH-GA80VB Cooling Heating Function Single phase Power supply 230V, 50Hz Capacity Dehumidification — Air flow(High/Low) K /h 2,940/1,470 2,940/1,470 Power outlet Running current 14.42 15.19 Power input 3,191 3,361 Power factor Starting current Compressor motor current 13.85 14.62 Fan motor current 0.57 Coefficient of performance(C.O.P)
NOISE CRITERIA CURVES MUH-GA60VB MUH-GA50VB FAN SPEED SPL(dB(A)) LINE FAN SPEED SPL(dB(A)) LINE High High Test conditions, Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24: Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24: Heating : Dry-bulb temperature 7: Wet-bulb temperature 6: Heating : Dry-bulb temperature 7: Wet-bulb temperature 6: NC-70 NC-70...
OUTLINES AND DIMENSIONS MUH-GA50VB Unit: mm REQUIRED SPACE Drainage hole [16.2 Air in Air in Drainage Air out 3holes [33 Service panel Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35 Gas refrigerant pipe joint Refrigerant pipe (flared) [12.7 MUH-GA60VB MUH-GA80VB Open as a rule 500mm or more if REQUIRED SPACE...
WIRING DIAGRAM MUH-GA50VB 21S4 RT61 INDOOR UNIT CN661 CN721 1 2 3 4 CONNECTING CN711 CIRCUIT BREAKER SR61 POWER SUPPLY 230V 50Hz TAB20 DEICER P.C. BOARD SYMBOL NAME SYMBOL NAME SYMBOL NAME COMPRESSOR CAPACITOR TERMINAL BLOCK OUTDOOR FAN MOTOR (INNER PROTECTOR) TB1,TB2 OUTDOOR FAN CAPACITOR VARISTOR...
Page 11
MUH-GA80VB RT61 RT62 RT63 CIRCUIT BREAKER CN711 CN661 CN662 CN724 1 2 3 CN721 SR62 SR61 21S4 TAB52 CN730 DEICER NR61 P.C. BOARD SYMBOL NAME SYMBOL NAME SYMBOL NAME CZ SURGE ABSORBER TERMINAL BLOCK OUTDOOR FAN MOTOR (INNER PROTECTOR) COMPRESSOR CAPACITOR NR61 VARISTOR TERMINAL BLOCK...
Page 14
MAX. REFRIGERANT PIPING LENGTH Refrigerant piping Piping size O.D : mm Model Max. length : m Liquid MUH-GA50VB 12.7 6.35 MUH-GA60VB 15.88 MUH-GA80VB 9.52 MAX. HEIGHT DIFFERENCE Indoor unit wMax. Height Refrigerant Piping difference: 10m(MSH-GA50/GA60VB)/ Max. Length 15m(MSH-GA80VB) Outdoor unit w Height difference should be within 10m(MSH-GA50VB/GA60VB)/ 15m(MSH-GA80VB) regardless of which unit, indoor or outdoor position is high.
PERFORMANCE CURVES MUH-GA50VB MUH-GA60VB MUH-GA80VB The standard specifications apply only to the operation of the air conditioner under normal conditions, since operating condi- tions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
Page 16
26.6 36.8 38.4 24.5 34.0 35.5 22.5 31.1 32.5 20.4 28.3 29.6 18.4 25.5 26.6 16.3 22.6 23.6 14.3 19.8 20.7 12.3 17.0 17.7 NOTE:The above curves are for the heating operation without any frost. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation 1 1 Both indoor and outdoor unit are under the same temperature/humidity condition.
SERVICE FUNCTIONS MUH-GA50VB MUH-GA60VB MUH-GA80VB 9-1. COMPULSORY DEFROSTING MODE FOR SERVICE By short circuit of the connector JPDS and JPSG(MUH-GA50VB)/ JPG1 and R871(MUH-GA60/GA80VB) on the outdoor deicer P.C. board, defrosting mode can be accomplished regardless of the defrost interval restriction. (Refer to 10-5.) Defrost thermistor RT61 must read below -3°C.
Page 26
10-2. Instruction of troubleshooting Start Indoor unit Indoor unit Indoor unit operates. OPERATION INDICATOR operates. doesn't receive Outdoor unit lamp on the indoor unit is Outdoor unit the signal from doesn't operate flashing on and off. doesn't remote controller. normally. operate.
Page 27
10-3. Trouble criterion of main parts MUH-GA50VB MUH-GA60VB MUH-GA80VB Part name Check method and criterion Figure Measure the resistance with a tester. (Part temperature –10˚C ~ 40˚C) Defrost thermistor (RT61) Refer to 10-5. "Test point diagram and voltage", "Outdoor deicer P.C. board", the chart of thermistor.
10-4. Troubleshooting flow Compressor and/or outdoor fan motor doesn’t operate. A A Check of outdoor unit MUH-GA50VB Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes. Compressor Rectify the indoor and doesn't operate.
Page 29
MUH-GA60VB MUH-GA80VB Turn ON the power supply. Is there 230V AC to Check the outdoor power supply between on the and connection of wiring. outdoor terminal block Compressor does not operate. Is there 5V DC between Is there 230V AC between Rectify the connecting CN730 1-3 on the deicer J101...
Page 30
Compressor and/or outdoor fan motor doesn’t stop. B B Check of outdoor unit MUH-GA50VB Turn OFF the power supply. After 1 minute, turn ON power supply again. Is there 230V AC between 3 on the Does compressor stop? compressor contactor (52C) and N on the Rectify the connecting wire.
Page 31
Unit operates COOL mode even if it is set to HEAT mode. Check of R.V. coil w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit. Disconnect the TAB52 on the deicer P.C. board. (MUH-GA60/GA80VB) Turn ON the power supply and operate the indoor unit in HEAT mode by pressing the EMERGENCY OPERATION switch.
Page 32
When OPERATION INDICATOR lamp flashes 10-time. Heating/ Cooling doesn't operate. Check of LEV (Expansion valve) MUH-GA80VB Turn ON the power supply. 1 During pressing both the OPERATION SELECT button and the TOO COOL button on the remote controller at the same time, press the RESET button.
Page 33
10-5. Test point diagram and voltage MUH-GA50VB Outdoor deicer P.C. board CN711 CN721 Power supply input Outdoor fan motor R.V. coil 230V AC 230V AC 230V AC NR61 Varistor Fuse 2A/250V R601 5~10V DC Defrost interval time short pin (JPDS, JPSG) (Refer to 9-1.) Jumper wire for change in defrost...
DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
Page 36
OPERATING PROCEDURE PHOTOS 3. Removing the propeller and the outdoor fan motor (1) Remove the cabinet. (Refer to 1.) Photo 4 Set screws of the (2) Remove the propeller nut and the propeller. outdoor fan motor Propeller NOTE : Loose the propeller in the rotating direction for Lead clamps removal.
Page 37
11-2. MUH-GA60VB MUH-GA80VB NOTE : These photos are MUH-GA80VB. OUTDOOR UNIT MUH-GA60VB is almost the same as MUH-GA80VB. OPERATING PROCEDURE PHOTOS 1.Removing the cabinet Photo 1 Screw of the top panel (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover.
Page 38
OPERATING PROCEDURE PHOTOS 3. Removing the propeller and the outdoor fan motor Photo 5 (1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut and the propeller. NOTE : Loose the propeller in the rotating direction for Set screws of the removal.
PARTS LIST (non-RoHS compliant) MUH-GA50VB 12-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol Part No. Part Name in Wiring Remarks MUH-GA50VB - Diagram E02 817 233 BACK PANEL E02 817 232 CABINET...
Page 40
PARTS LIST (non-RoHS compliant) MUH-GA60VB 12-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS...
Page 41
PARTS LIST (non-RoHS compliant) MUH-GA60VB 12-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol in Wiring Part No. Part Name Remarks MUH-GA60VB - Diagram E02 819 297 TOP PANEL E02 821 630 OUTDOOR HEAT EXCHANGER...
Page 42
PARTS LIST (non-RoHS compliant) MUH-GA80VB 12-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS...
Page 43
PARTS LIST (non-RoHS compliant) MUH-GA80VB 12-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol Remarks Part No. Part Name in Wiring MUH-GA80VB - Diagram E02 819 297 TOP PANEL E02 819 309 THERMISTOR...
Page 44
PARTS LIST (non-RoHS compliant) MUH-GA50VB MUH-GA60VB MUH-GA80VB 12-4. ACCESSORY Q'ty/unit Symbol in Wiring Remarks Part No. Part Name MUH-GA60VB MUH-GA50VB MUH-GA80VB Diagram E02 817 704 DRAIN SOCKET [33 2PCS/ SET E02 444 705 DRAIN CAP E02 444 706 DRAIN CAP...
RoHS PARTS LIST (RoHS compliant) MUH-GA50VB 13-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS...
Page 47
RoHS PARTS LIST (RoHS compliant) MUH-GA50VB 13-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol MUH-GA50VB in Wiring Part No. Part Name Remarks Diagram E12 817 233 BACK PANEL E12 A27 233 BACK PANEL...
Page 48
RoHS PARTS LIST (RoHS compliant) MUH-GA60VB 13-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS...
Page 49
RoHS PARTS LIST (RoHS compliant) MUH-GA60VB 13-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol in Wiring Remarks Part No. Part Name MUH-GA60VB - Diagram E12 819 297 TOP PANEL E12 821 630 OUTDOOR HEAT EXCHANGER...
Page 50
RoHS PARTS LIST (RoHS compliant) MUH-GA80VB 13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS...
Page 51
RoHS PARTS LIST (RoHS compliant) MUH-GA80VB 13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol Remarks Part No. Part Name in Wiring MUH-GA80VB - Diagram E12 819 297 TOP PANEL E12 819 309 THERMISTOR...
Page 52
E12 444 706 DRAIN CAP HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN C C Copyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in May 2007. No.OB368 REVISED EDITION-B 6 Distributed in Jun. 2006. No.OB368 REVISED EDITION-A 6 New publication, effective May 2007 Distributed in Oct.