Split-type Air-Conditioner MXZ-3B54VA MXZ-3B68VA MXZ-4B71VA INSTALLATION MANUAL English • Refer to the installation manual of each indoor unit for indoor unit in- stallation. Deutsch Français Nederlands Español Italiano Português Dansk CONTENTS Svenska 1. BEFORE INSTALLATION ................2 2. OUTDOOR UNIT INSTALLATION ..............5 Türkçe...
Rated Fre- Breaker Max. Refrigerant adjust- Voltage connecting wire height difference MXZ-3B54VA 15 m 4-core MXZ-3B68VA 25 A 3-core 2.5 mm 15 m to interrupt the source power phase. (When the power switch is shut off, it installation manual of the indoor unit.
1-4. SELECTING PIPE SIZE AND OPTIONAL DIFFERENT-DIAMETER JOINTS units according to the following table. • If the diameter of connection pipes does not match the diameter of pipe end connections, use optional different-diameter joints. Indoor unit Outdoor unit MXZ- MXZ- MXZ- 3B54VA 3B68VA...
1-6. INSTALLATION DIAGRAM ACCESSORIES Check the following parts before installation. Drain socket Drain cap no gap. PARTS TO BE PROVIDED AT YOUR SITE When the piping is to be at- tached to a wall containing metals Wall hole cover Piping tape Extension drain hose (or soft PVC hose, 15 mm inner around the piping.
2. OUTDOOR UNIT INSTALLATION Terminal block 2-1. CONNECTING WIRES FOR OUTDOOR UNIT to the connecting section of the terminal block. with the cable clamps. TION is completed. Service panel wire with cable clamps. <OUTDOOR UNIT> Terminal Terminal Terminal Terminal Terminal block for block block block...
3-2. PIPE CONNECTION cause refrigerant leakage. Outdoor unit connection WARNING Connect pipes to stop valve pipe joint of the outdoor unit in the same When installing the unit, securely manner applied for indoor unit. connect the refrigerant pipes before • For tightening, use a torque wrench or spanner and use the same starting the compressor.
Page 7
4-3. REMOVING THE MAINTENANCE PANEL The setting of Dip Switch on the outdoor controller board can be changed without removing the front panel. Follow the procedures below to remove the maintenance panel and set the Dip Switch. Note: could cause malfunction. maintenance panel 4-4.
4-6. TEST RUN unit connecting wires. Make sure that the following is done. • Power is supplied to the unit. • Stop valves are open. About the restart protective mechanism Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 4-7.
Page 9
• Low Voltage Directive 2006/95/ EC the following EU regulations: • Electromagnetic Compatibility Directive 2004/108/ EC HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN AUTHORIZED REPRESENTATIVE IN EU: MITSUBISHI ELECTRIC EUROPE B.V. JG79A237H01 HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K.