® Product Manual ABB i-bus Light Controller with Sensor LR/S with LF/U Intelligent Installation Systems...
Page 2
This manual describes the function of the Light Controller LR/S x.16.1 with the corresponding Light Sensor LF/U 2.1 with the application program Control Dim xf 1-10V/1.0 (x = 2 and 4 outputs). Subject to changes and errors excepted. Exclusion of liability: Despite checking that the contents of this document match the hardware and software, deviations cannot be completely excluded.
1-10V interfaces – be introduced as a master in a KNX lighting ® system which integrates a wide range of components, e.g. ABB i-bus Switch/Dim Actuators SD/S, DALI Gateways DG/S or Universal Dim Actuators UD/S, into an energy efficient constant lighting control system.
(MDRC) in ProM Design for installation in the distribution ® board on 35 mm mounting rails. The connection to the ABB i-bus implemented via a bus connection terminal on the device shoulders. The LR/S can control dimmable electronic ballasts or transformers with a 1-10 V interface via two or four outputs –...
Page 12
320 A (600 μs) Maximum peak inrush-current I 200 A 18 W (ABB EVG 1 x 58 CF) Number of electronic ballasts (T5/T8, single element) 24 W (ABB EVG-T5 1 x 24 CY) 36 W (ABB EVG 1 x 36 CF)
Page 13
The programming requires ETS2 V1.3 or higher. If ETS3 is used a *.VD3 or higher type file must be imported. The application program for the ETS2/ETS3 can be found at ABB/Lighting Devices/Illumination and Light Sensors/Control Dim xf 1-10V/1, (x = 2 or 4, number of outputs).
Device technology Assembly and installation The ABB i-bus Light Controllers LR/S x.16.1 are suitable for installation in the distribution board or small enclosures for fast installation on 35 mm mounting rails to DIN EN 60 715. The mounting position of the Light Controller can be selected as required and no auxiliary voltage is required.
KNX device ® The assignment of the address of the ABB i-bus Light Controller is carried out via the ETS and the programming button on the device. The device features a programming button located on the edge of the device for assignment of the physical device address.
You will require a PC or Laptop for parameterisation with the ETS (from ® ETS2 V1.3) and a connection to the ABB i-bus , e.g. via an RS232 or USB interface. If ETS3 is used a *.VD3 or higher type file must be imported.
1-10 V devices which are connected to the output of the LR/S x.16.1. Via the master/slave function additional luminaries can be integrated into the lighting ® control of the LR/S, e.g. DALI luminaries via an ABB i-bus DALI Gateway ®...
In slave mode the output of the Light Controller follows the brightness value provided by the master output via the object Brightness value of slave. ® In this way the output of another ABB i-bus device can be integrated into the constant lighting control of the Light Controller.
Page 96
255 = 100 % Via the master/slave function additional luminaries can also be integrated with the Light ® Controller of the lighting control of the LR/S, e.g. DALI luminaries via an ABB i-bus DALI ® Gateway DG/S or other 1-10 V luminaries via the ABB i-bus Switch/Dim Actuators SD/S.
Maximum peak inrush-current I If these limit values are exceeded the relay will be destroyed, e.g. it will weld. Example ABB EVG 1 x 58 CF: Peak inrush current Ip = 33.9 A (147.1.μs) For the LR/S 4.16.1 Light Controller this means:...
The information (brightness value and transition time) is not stored in the ® pushbutton, but rather in the Light Controller and the other ABB i-bus devices in the system. All scene devices, such as an output of the Light Controller, are addressed by the same group address. It is sufficient to send a single telegram to recall the scene with all outputs involved.
Page 119
This behaviour ensures that only energy necessary to ensure the optimum level of brightness is used. The energy consumption can be reduced further ® if additional presence detectors, e.g. ABB i-bus Presence Detectors BW/S or Presence Detector PM/A are integrated into the system. In this way the light and the light control can only be switched on if there are persons located in the room.
Page 122
Further luminaries can be integrated into the constant lighting control which are not directly connected to the Light Controller. These for example, can be ® DALI lamps via an ABB i-bus KNX DALI Gateway or a dimmer. These components are controlled directly as so-called slaves directly by the Light Controller (= master).
This is not an ABB-specific phenomena bit rather is the case for all constant lighting controls which function according to this principle. Different lighting technology terms are explained in the following to improve understanding of what is involved.
® ABB i-bus Appendix LR/S x.16.1 scope of delivery The ABB i-bus® KNX Light Controller LR/S is supplied together with the following components. Please check the items received using the following list. • 1 pcs. LR/S x.16.1 , MDRC •...