It is the sole responsibility of the buyer of the products to provide and continuously ensure a secure connection between the product and the system network and/or any other networks that may be connected to the product. ABB is in no event liable for the security of the network used by buyer.
3. Power electronics and cabinet features ..........39 3.1. Drive system topology ..............39 3.1.1. Drive ..................39 3.1.1.1. ACS6080 cabinet units ........... 41 3.1.1.2. Final drive configuration ..........41 3.1.2. Motor ..................41 3.2. Standard cabinet units ..............42 3.2.1.
Page 4
Access to the cabinets ............78 5.3.3. Cabinet roof ................78 5.3.4. Fire protection ................. 78 5.3.5. Cable duct material ............... 79 5.3.6. Installation material ..............79 5.3.7. Tools ..................79 PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 4/220...
Page 5
6.5. Cable entry systems ................117 6.5.1. Frames with type 1 sealing modules ........117 6.5.2. Frame with type 2 sealing modules ........119 6.5.3. Plates with cable glands ............119 PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 5/220...
Page 8
9.4.18. Replacing the fan unit in an EXU with a DCS880 H6 unit ..............215 9.4.19. Replacing the air-to-water heat exchanger of the EXU ................... 217 PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 8/220...
Page 9
Figure 3-21 EXU H4/T4 frame cabinet (A) and EXU H6 frame cabinet (B) ....60 Figure 3-22 CIU cabinet (A) and WCU800 cabinet (B) ..........62 Figure 3-23 ACS6080 example drive with air-to-air heat exchanger ......63 Figure 3-24 Auxiliary fan unit ..................64 Figure 3-25 Air circulation through ventilation grids in 600 mm COU (A), 1000 mm COU (B) and WCU800 (C) ................
Page 10
Figure 6-3 System ground connection (1) in a 600 mm TEU ........112 Figure 6-4 Grounding the EXU ..................113 Figure 6-5 Cable tray and cable ducts in an LSU (A = front) ........114 PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 10/220...
Page 11
Figure 6-34 Cable routing examples in an EXU cabinet with an ED5V, EB5R, EB5S, EB7P or EB7Q type DCS880/DCT880 converter (A) and in an EXU cabinet with an ED7Y type DCS880 converter (B) ..........139 PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 11/220...
1. About this manual 1.1. Product overview The ACS6080 is a medium voltage drive that can control any type of AC motor, including high-power induction, synchronous, and permanent magnet motors. The ACS6080 covers a power range of 3 - 36 MVA and delivers output frequencies of 0 - 75 Hz in the voltage range up to 3.3 kV.
(such as layout drawings, wiring diagrams, project-specific data, engineering notes). If information is required beyond the instructions in this manual, refer the matter to ABB. 1.3. Structure of the user documentation The documentation for a standard drive consists of this document and the following project-specific appendices.
The following table lists terms and abbreviations you should be familiar with when using this user manual. Some of the terms and abbreviations used in this user manual are unique to ABB and might differ from the normal usage. Table 1-1 Terms and abbreviations...
Page 20
Deutsches Institut für Normung Digital Output Drive Synonym for ACS6080 frequency converter Drive Composer Windows application for commissioning and maintaining ABB drives. Drive system The drive system includes all equipment for converting electrical into mechanical power to give motion to the machine. Direct-to-line...
Page 21
Term ABB’s S500 I/O system. An I/O device consists of a module termination unit (MTU) and one I/O module. I/O module Term of ABB’s S500 I/O system. The I/O module is an active input or output device for digital or analog signals. I/O station Term of ABB’s S500 I/O system.
Page 22
PUPA Pulse pattern Pulse width modulation German color standard Resistor Braking Unit Redundant Drive Control Redundant Drive Interface Receive Data Register Rolling Mill Drive PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 22/220...
Page 23
Term/ Definition Abbreviation Revolutions Per Minute S500 I/O The S500 I/O is a distributed process input output system that can be connected to various process controllers from ABB and other companies. Short-Circuit Synchronous Motor Semi-Redundant Drive Synchronous Serial Interface The SSI is a point-to-point, serial communication interface for digital data transmission between a master (eg, drive) and a slave (eg, sensor).
3BHS852904 E01 ACS6080 spare part packages 3BHS844005 E01 BCU-55 PP C932 A: Technical Description 3BHS813816 E01 ACS5000, ACS6000 and ACS6080 water cooling unit WCU800 3BHS821937 E01 user manual ACS5000, ACS6000 and ACS6080 water cooling unit WCU1400 3BHS835714 E01 user manual...
IMPORTANT! Commissioning of the drive must only be performed by qualified and certified ABB personnel. 1.6.1. Handling Personnel must be skilled and experienced in unpacking and transporting heavy equipment.
1.9. Quality certificates and applicable standards The following certificates and conformity declarations are available with ABB: – ISO 9001 and ISO 14001 certificates stating that ABB Switzerland Ltd has implemented and maintains a management system which fulfills the requirements of the normative standards –...
1.11. Tools ABB offers various tool sets containing all necessary tools and equipment for installation, commissioning and maintenance of the drive. The content of the tool sets is described in the Service Equipment manual.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Is used to address practices not related to physical injury, but which can result in equipment damage. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 29/220...
In case of fire in the drive room: • Observe the established rules and regulations for fire safety • Only allow firefighters with the appropriate PPE to enter the drive room PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 31/220...
IMPORTANT SAFETY INFORMATION 2.5. The 7 steps that save lives ABB’s 7 steps that save lives concept is a series of actions that must take place prior to commencing work on or near electrical installations. Prepare for the work: do an on-site risk assessment or job hazard analysis that considers the limits of approach for shock and arc-flash.
Page 33
Check the earths are properly applied • Answer specific questions from the working group • Ensure the work can proceed without danger • Complete and verify the “Permit to Work” PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 33/220...
• Wrong parameter settings • Software errors • Faulty hardware Hazardous substances can be emitted from drive system components, eg, due to Incorrect disposal of components PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 34/220...
Maximum safety trip time: 500 ms The maximum safety trip time is the maximum allowed time to ensure safe disconnection of the main power supply to prevent any hazard to personnel. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 36/220...
3) No further damage to the drive 4) No hazard to personnel 5) Maximum protection trip time 6) Maximum safety trip time In order to meet the stipulated safety requirements, ABB recommends one of the following: – MCB is equipped with 2 independent opening coils –...
– Motor 3.1.1. Drive The ACS6080 is a voltage source frequency converter for high-power induction and synchronous motors. The drive features a common DC bus permitting the configuration of single-motor or multi-motor solutions. Figure 3-1 Common DC-bus principle for single motor drive (A) and...
POWER ELECTRONICS AND CABINET FEATURES The drive has a flexible modular design with standard and optional cabinet units. Each cabinet unit is dedicated to a specific function. Figure 3-2 ACS6080 drive example 1) Active rectifier unit (ARU): 5) Water cooling unit (WCU):...
POWER ELECTRONICS AND CABINET FEATURES 3.1.1.1. ACS6080 cabinet units Standard cabinet units Optional cabinet units – Active rectifier unit (ARU) – Input reactor unit (IRU) – Inverter unit (INU) – Input filter unit (IFU) – Line supply unit (LSU) –...
These can only be closed if the DC-link capacitors have been discharged. For more information, see “8.5 EXU control panel” on page 153. Figure 3-9 CBU 1) Grounding switch 2) DC-link capacitor PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 46/220...
The speed and torque of the motor is controlled by Model Predictive Pulse Pattern Control (MP C). The MP C motor control platform is unique to ABB and has been proven in all variable speed drives of the ACS product range. MP C provides accurate speed and torque control, and high dynamic speed response.
Figure 3-12 Control panel Figure 3-13 Location of control panels on master COU (A) and slave COU (B) 1) Control panels PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 50/220...
The water cooling units are accessible for maintenance even when the drive is in operation. For more information, see: – “ACS5000, ACS6000 and ACS6080 water cooling unit WCU800 user manual” (3BHS821937 E01) – “ACS5000, ACS6000 and ACS6080 water cooling unit WCU1400 user manual”...
External cooling circuit: transfers the heat losses from the water-to-water heat – exchanger to the exterior. The water cooling units are pressurized and not open to atmospheric pressure. Figure 3-15 Cooling circuit in an ACS6080 drive 1) Return pipes 6) Heat exchanger 2) LSU...
POWER ELECTRONICS AND CABINET FEATURES 3.3.4. Braking units A braking chopper unit (BCU) and a resistor braking unit (RBU) are available for the ACS6080. Table 3-5 BCU braking power Braking resistor (ohm) Single braking power (kW) Double braking power (kW)
An RBU, with integrated resistors, is used for smaller braking capabilities. DC (+) DC (NP) DC (-) Figure 3-20 RBU cabinet (A) and circuit diagram (B) 1) IGCT 2) Water-cooled resistor PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 59/220...
For more information, see “8.5 EXU control panel” on page 153. 3.3.5.2. Output disconnector The optional output disconnector is used to disconnect the EXU from the motor for maintenance purposes. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 61/220...
For information on number and location of heat exchangers and transformer, see “Appendix C - Mechanical drawings”. The number of installed air-to-air heat exchangers and transformers depends on the configuration of the drive. Figure 3-23 ACS6080 example drive with air-to-air heat exchanger 1) Air-to-air heat exchanger 2) Additional transformer PRODUCT DOCUMENT KIND DOCUMENT ID.
Figure 3-25 Air circulation through ventilation grids in 600 mm COU (A), 1000 mm COU (B) and WCU800 (C) NOTE – The number of fans varies depending on the cabinet. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 64/220...
POWER ELECTRONICS AND CABINET FEATURES 3.5. Cabinet design The cabinet has been designed using the modular cabinet system of ABB and fulls the requirements of international standards. The design consists of a skeletal frame made of galvanized steel where the outer panels made of 1.5 mm thick painted galvanized steel are bolted to.
3.6. Door locking system For more information on the door locking system, including grounding switches, locking bars, and safety switches, see “8.5 EXU control panel” on page 153. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 66/220...
MCB requirements are described in “2.7 Important note - main circuit breaker” on page 35. Based on the ACS6080 IAC rating, the minimum approach distance is 0.3 m. Local rules may require additional distance. The user is responsible to determine the correct approach distance considering local rules.
The PE and PG busbar connect inside the capacitor bank unit, which has the grounding switch on the front door. The connection is made in the factory. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 68/220...
3. Compare the complete delivery with the purchase order and the packing list. 4. If parts are missing or damaged, immediately inform the shipping company and the ABB service organization. It is recommended to photograph the damages and send the photographs to ABB.
Page 70
All of the transport units for a drive have the same converter number, in this case, “Converter 1”. The item number in the “ABB Item / Customer item” column of the packing list provides information about separately delivered crates with accessories such as tools and installation material.
NOT lift and move them with a crane. • Use appropriate transport means, such as heavy load hydraulics rollers or air cushions. If in doubt, contact ABB for instructions. – To prevent damage to drive components, transport and move the drive or a transport unit only in upright position.
TRANSPORTATION, STORAGE AND DISPOSAL 4.5.1.1. Lifting recommendations Refer to Fig. 4-1 and Fig. 4-2 when following these ABB recommendations: – Use a lift frame or a lift spreader with the crane. – Use lifting equipment (eg, web slings, chain slings, round slings, safety hooks, shackles) that corresponds to the weight that is to be lifted.
4.6. Storage The drive can be stored for up to one year in the original packaging as long as it is not damaged or opened. For information on longer storage periods, contact the ABB service organization. 4.6.1 Storage conditions The minimum requirements for storage are based on IEC 60721-3-1.
4.6.3.1. Warranty information IMPORTANT! Check the spare parts immediately after receipt for damages and report any damage to the shipping company and the ABB service organization. Observe the following to maintain spare parts in good condition and to keep the warranty valid during the warranty period: –...
Dispose of the packaging materials and components at the end of the life time of the drive according to local regulations. For more information on the disposal of packaging materials and drive components, see the recycling instructions. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 76/220...
DO NOT install any foreign objects on the roof and do not step on roof. 5.3.4. Fire protection To prevent fire from spreading into the drive, apply suitable fire protection measures. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 78/220...
WCU. Installation material such as counter-flanges, bolts, nuts and seals are supplied. For information on dimensions of the raw water entry and the flanges, see “Appendix C - Mechanical drawings”. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 79/220...
3. Line-up the transport units as shown in “Appendix C - Mechanical drawings”. NOTE – The units can be lined-up either beginning from the left or the right. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 80/220...
Page 81
Cabinet doors are not misaligned and that there are no gaps between cabinet walls and cabinet frame – Adjoining surfaces of transport units meet perfectly all around PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 81/220...
In such cases, you only need to join the connection points that you can access. Figure 5-1 Connection point locations on transport units 1) Connection point locations 2) M6 x 16 (9ABA450093R0259 SCR-CBS-M6X16-8_8-FLZNNC) PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 82/220...
NOTE – The sealing lip can touch the pipe end. 3. Turn and move the pipe joint smoothly. 4. Clean the pipe joint and treat the bolts with an appropriate lubricant before refitting. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 84/220...
Use a conical spring washer on each side of a connection. Figure 5-3 Bolted busbar connection 1) Hex-head bolt 3) Flange nut 2) Conical spring washer PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 85/220...
2. Loop the cables as illustrated and fasten them to the cable tie mounts (circles). 3. Loop a length of the cables and fasten them to the cable tie mount (circle). PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 95/220...
5. Lift the heat exchanger above the opening in the roof and orientate the heat exchanger with the LEDs (circle) pointing to the front of the cabinet. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 96/220...
Page 97
6. Route the cables through the designated openings (circle) at the front of the cabinet. 7. While lowering the heat exchanger onto the roof, pull the cables through the openings. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 97/220...
15 x 11. In the lower part (2), tie the cables together at regular distances. 12. Check that the cables do not touch the DC busbars. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 98/220...
Air-to-air heat exchangers must be removed and refitted where two transport units are joined. Depending on the drive configuration, at least one heat exchanger must be removed for joining the DC busbars of two adjacent transport units. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 99/220...
2. Remove the cable ties. 3. Lift the heat exchanger by crane and move it approximately 20 cm to the back and place it on pieces of square timber. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 100/220...
4. Fix the cables with cable ties at regular distances of approximately 20 cm. 5. Tighten all screws of the heat exchanger. 6. Fix the cables inside the terminal box with cable ties. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 101/220...
Pressure relief vents are installed on the roofs of TEUs and COUs. Figure 5-18 Pressure relief vents • Weight: ~26 kg • Length: 840 mm • Width: 520 mm • Height: 210 mm PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 103/220...
1) Orientation of baffle blades 3) Pressure relief vents 2) Center of drive 2. Fasten the pressure relief vent to the roof with the supplied screws (Fig. 5-20). PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 104/220...
3. Attach the tape on the whole length of the joining crossbars (1). Figure 5-21 Attach sealing tape to the joining crossbar (1) 4. Reinstall the roof plates. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 105/220...
Install the joints at the front and the back of the roof of two adjoining transport units using the supplied installation material. NOTE – The joints (1) within a transport unit are factory-installed. Figure 5-22 Roof joints (1) PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 106/220...
1) Two struts at 45° to ceiling 3) Do not install the struts at a 90° angle to the cabinet roof 2) One strut at 90° to wall PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 108/220...
– DO NOT switch on the main and auxiliary power supplies during the installation. – After the installation, obtain permission from the ABB commissioning personnel BEFORE switching on the the main and auxiliary power supplies. Overview The installation includes the following items: –...
Synchronization cables are used in drives with an ARU. A shielded, 3-phase cable without neutral wire is required for the supply voltage of the synchronization transformer. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 110/220...
Cable shields are connected to the separate PG ground busbar. The connection between the PE and PG ground busbars inside the CBU is made in the factory. The CBU has a grounding switch on the door. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 112/220...
Wiring list in “Appendix D - Wiring diagrams”. The data provide information on: – Cable identification – Cable type – Cross-sectional area – Location of terminals PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 113/220...
RBU, BCU and VLU, make sure that the cables are at a minimum distance of 5 mm from the closest metal part. 3. Connect all cables and wires according to the “Converter Hardware” diagram. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 114/220...
Arc Guard unit TVOC-2 with HMI panel – Optical fiber detectors: pre-installed in the relevant cabinets with the corresponding optical fibers coiled up beside the detectors (Fig. 6-7). PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 115/220...
2. Lay the cables into their designated trays and cable ducts as seen in Fig. 6-8. 3. Connect the cables to the arc monitor located in the REB according to the drawings. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 116/220...
Power cables, ground cables, bonding conductors – Auxiliary power cables, control cables Included in delivery – Undrilled gland plate Not included in – Cable glands delivery – Tools – Accessories PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 119/220...
In the openings facing the back wall of the TEU, place the compression wedge (4) between the frame (1) and the sealing module (5). This ensures that the minimum distance to the high-voltage busbars is maintained. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 120/220...
2) Remove these bolts 5) 17 mm and 19 mm 3) Bottom bracket 4. After you have routed the cables, install the busbars in the reverse order of removal. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 122/220...
DCS880 H4/DCT880 T4 unit” on page 212. 4. Unplug the fan power supply cables and the tube from the air pressure switch. Figure 6-17 EXU cabinet 1) Front cover 2) Pull relief PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 123/220...
1. Determine the required length of a cable between the point of entry and the connection point inside the cabinet. 2. Cut the cable to the required length before connection. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 124/220...
M12 bolt 7) Outer cable sheath 12) Sheath seal 2. Install the sealing modules according to the instructions of the sealing module supplier. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 125/220...
EXU. 1. Remove the grommets from the entry plate. 2. To ensure proper sealing, cut along the marking that corresponds to the cable diameter. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 126/220...
3. Choose the length and the orientation of the bolts so that the distance between bolted joints of different phases is not less than 25 mm. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 128/220...
If a coated nut (eg, with bonded molybdenum-disulfide [MoS ] coating) is used, the connection does not need to be lubricated. 6.7.5.4.4 Tightening torque ABB recommends a tightening torque of 40 Nm for M12 bolts. For other sizes, follow the manufacturer’s recommendations. PRODUCT DOCUMENT KIND DOCUMENT ID.
1. Determine the required length of a cable between the point of entry and the connection point inside the cabinet. 2. Cut the cable to the required length before connection. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 131/220...
NOTE – If cables are routed through the cabinet floor, the grommets can be discarded. 4. If necessary, remove the entry plate and pull the cable through the entry holes. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 133/220...
The serial communications and encoder cables are connected inside a COU. Top and bottom cable entries are covered with blanking plates. Materials for cable fitting, EMC requirements and sealing are not supplied. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 135/220...
1) Bottom blanking plate 2) Front 2. Prepare the length of cable that passes through the cable entry according to “6.8.3 Preparing cables for cable glands” on page 133. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 136/220...
If a twisted pair cable is used, leave the unshielded cable ends twisted until they reach the terminals. Leave unshielded conductor ends as short as possible (< 50 mm). PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 137/220...
Cable entries with cable glands: “6.8.3 Preparing cables for cable glands” on page 133. NOTE – Materials for cable fitting, EMC requirements and sealing are not supplied for undrilled plates. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 138/220...
4) Terminal strip for auxiliary power and control cables 5) Auxiliary supply cable 4. Connect the cables to the terminals inside the terminal compartment of the cabinet. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 139/220...
1) DCS880/DCT880 control panel 3) Indentation 2) Removable front cover 3. Insert a flat-blade screwdriver into one of the indentations at the bottom of the DCS880/DCT880 front cover. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 140/220...
7) Optical fibers to DCS880/DCT880 converter Figure 6-37 Cable routing example in an EXU cabinet with an ED5V, EB5R, EB5S, EB7P and EB7Q type DCS880/DCT880 converter PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 141/220...
2. Connect the two optical fibers to the receptacles of slot 1 according to the terminal numbers printed on the marker sleeves. Figure 6-39 1 Control unit SDCS-CON-H01 1) Slot 1 (FDCO-01 module 2) Control panel PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 142/220...
3) Cable enters through the floor 7) Optical fibers to DCS880/DCT880 D4 converter 4) Terminal strip for auxiliary power and control cables 4. Reattach the DCS880/DCT880 cover. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 143/220...
If EMC entry plates with grommets are used, check that the grommets fit tightly (arrows) to prevent water entering the cabinet. • If necessary, seal gaps with silicone. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 144/220...
ABB. 7.2. Commissioning procedure Information on the commissioning procedure and the start conditions for commissioning can be obtained from ABB. 7.3. Commissioning checklist In order to ensure uncomplicated and speedy commissioning, it is important that drive and associated equipment are ready for commissioning.
Types and cross sections of control cables suitable for the signal type and signal level. □ Types and cross sections of power cables selected according to the ABB power cable specification. □ Pulse encoder cable shields are connected to the shield earthing point and not connected directly to the pulse encoder interface (applies only to drives with pulse encoder interface).
Sufficient quantity of deionized water according is available. (see “Appendix C - Mechanical drawings”). □ Air conditioning of drive room ready for load run of drive □ 4) Optional equipment (eg, chiller) ready PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 148/220...
OPERATION 8. Operation 8.1. Overview This chapter describes how to operate an ACS6080 drive from an assistant control panel on a control unit of the drive, ie, local operation. Figure 8-1 Assistant control panel NOTE – Control of the drive via a PLC or higher-level control system is not described in this chapter.
For instructions on how to use the assistant control panel, see the “ACX-AP-x Assistant control panels user manual” (3AUA0000085685). ACS6080 Figure 8-2 Assistant control panel front and back 1) Display...
The illuminated push buttons on the doors can be tested with the lamp test function as described in the firmware manual, see “Appendix G - Signal and parameter table”. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 151/220...
8.4.2.1. Lamp test The illuminated push buttons on the doors can be tested with the lamp test function as described in the firmware manual. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 152/220...
– Actual converter current in A (rectified AC current value) When the control panel has been set to remote, the START / STOP keys become inoperable. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 153/220...
– The parameters are set as required for operation and verified during commissioning and must NOT be changed afterward PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 154/220...
The indicator lamp for the grounding switch and the white lamp (Fig. 8-6) have an integrated momentary push button. The lamps light up when the lamp cap is pressed. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 155/220...
NOTE – For more information, see “9.4.4 Unlocking and opening the doors” on page 180. 1) Locking bar in locked position 3) Safety switch 2) Locking bar in unlocked position Figure 8-7 Safety switches PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 156/220...
For more information, see “9.4.9 Drives with the manual output isolation (optional)” on page 189. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 157/220...
The status message always alternates with the specific fault message. The type of shutdown depends on the fault class the fault condition is assigned to in the drive software. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 158/220...
Only in drives with an ARU Ready run • INU starts magnetizing (only in drives with an ARU) • INU starts to modulate 8) Start command 9) Ready ref 10) Operation PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 159/220...
• Drive is grounded • Doors in medium voltage units are released for opening • Auxiliary power supply switched off 9) Not ready to switch on PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 160/220...
All locking screws have been removed from the locking bars on the inside of the doors of medium voltage compartments. – Doors are closed and locked or bolted. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 162/220...
If a fault cannot be reset, the responsible personnel must rectify it. • (Drives with an ARU) When faults are present and the drive is ready, the INU is “Ready to switch on”. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 163/220...
Page 164
When the motor has finished magnetizing, the run status message lights up permanently. The drive is now in “Ready ref” to indicate that the drive system is operating. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 164/220...
When an emergency-off is initiated during operation, the following sequence of events occurs: MCB opens Drive system coasts down DC-link of the drive discharges EMERGENCY-OFF RESET button flashes SUPPLY OFF push button flashes PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 165/220...
8.11. Arc detection with the Arc Guard System™ (optional) The optional Arc Guard System™ detects fast arc faults in the terminal sections of an ACS6080 drive. When the Arc Guard System detects an arc fault the drive performs protection firing and immediately opens the main circuit breaker.
6. Reset the fault on Arc Guard HMI panel. 7. Acknowledge the firing through with parameter 16.26 on the control panel (only when fault was understood and corrected). 8. Restart the drive. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 167/220...
ABB service personnel. After the warranty period, repair work must be carried out by certified personnel. 9.1.1. Required qualification To maintain safe and reliable operation of the drive, ABB recommends taking out a service contract with the ABB service organization. 9.1.2. Maintenance schedule Carry out all maintenance tasks according to the maintenance schedule, on time and at the stated intervals in the “ACS6080 preventive maintenance schedule”...
Figure 9-2 Cable and wire designation 1) Wire number 2) Terminal number 9.2.2.1. Understanding wiring diagrams For information on item designation and cross-reference conventions, see “Appendix D - Wiring diagrams”. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 170/220...
MCB when a fault condition occurs. A fault condition must be corrected and the fault be manually reset before the drive can be started again. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 171/220...
The data logger provides information (eg, waveforms of voltage, current, torque) for efficient troubleshooting. Contact ABB service if a fault cannot be rectified. When calling ABB service, it is recommended to have the following data available at the time when the fault occurred: •...
STATUS: A B C D E F G H I J K L Figure 9-3 Assistant control panel (A) and BCU-55 control unit: front view (A) and rear view (B) 1) LEDs PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 173/220...
3) Red LED off (A) and Green LED off (B): exchanger is healthy Auxiliary voltage is missing 2) Red LED on (A) and Green LED off (B): Alarm conditions PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 174/220...
300 V (DC) over ground. – Wait 5 minutes for the capacitors to discharge. – Before touching a capacitor, verify that the capacitors are discharged. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 175/220...
The motor stops according to the preset stop function. When the motor has reached zero speed, the drive is in “Ready run. 3. Press the SUPPLY OFF push button to disconnect the drive from the main power supply. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 176/220...
8. Switch off and lock out all auxiliary voltages from external sources. 9. To connect a grounding set, continue with “9.4.8 Connecting a grounding set” on page 186. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 178/220...
Drive status is “Ready to switch on” IMPORTANT! If you cannot turn the grounding switch, continue with “9.4.7 Emergency release of a door safety switch” on page 184. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 179/220...
NOTE – If the white lamp does not turn on, continue with “9.4.6 Testing the white lamp” on page 183. Figure 9-8 Grounding switch grounded 1) White lamp 2) Yellow lamp PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 180/220...
Page 181
5. If you cannot open the door, continue with “9.4.7 Emergency release of a door safety switch” on page 184. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 181/220...
• Door hinged on the right: IMPORTANT! A limit switch monitors the locked position. If a door is not locked properly, you cannot start the drive. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 182/220...
If the LED is lit, the drive control system receives the feedback signal "grounding switch is closed", but the control system has not released the doors. • If the LED is not lit, the feedback signal is missing. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 183/220...
2. Loosen the locking screw (1) until the release dial can be turned. 3. Turn the release dial from the locked to the unlocked position. 5 mm You can now actuate the locking bar and open the doors. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 185/220...
2) Enclosure ground clamp Depending on the type of line-side rectifier, continue with: – “9.4.8.1 Drives with LSU” on page 187 – “9.4.8.2 Drives with ARU” on page 188 PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 186/220...
Figure 9-16 Tools for removing the busbar connectors 1) Orientation of lever for removing busbar 3) Four-way grounding set (4x) connectors 2) Orientation of lever for fitting the busbar connectors PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 190/220...
COU1 LSU2 Figure 9-17 Overview of grounding the drive - INU1 is shut down (A) and INU2 is shut down (B). Numbers indicate the connection sequence. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 191/220...
9. Check that the power operating mode (POM) of the drive corresponds to the busbar connectors fitted. 10. Start the drive according to the established procedures. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 193/220...
7. Check that the power operating mode (POM) of the drive corresponds to the busbar connectors fitted. 8. Start the drive according to the established procedures. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 194/220...
NOTE – To disconnect the water hose, pull the locking sleeve of the coupling towards the front of the cabinet (arrow). 2. Cut off the cable ties (1) and disconnect the optical fibers and the power supply leads (2). PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 195/220...
CAUTION! A phase module weighs approximately 190 kg. When pulling out the phase module, make sure that the disconnected water hoses, optical fibers and power supply leads are out of the way. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 196/220...
NOTICE DO NOT mix up the cables. The identification on the label must correspond to its counterpart on the phase module. Verify the correct connection with the corresponding wiring diagram. 10. Fasten the cables with cable ties. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 197/220...
PREVENTIVE AND CORRECTIVE MAINTENANCE 9.4.11. Visual checks on the drive Check the drive and its immediate vicinity visually at the intervals stated in “ACS6080 preventive maintenance schedule” (3BHS838899 E01) and pay attention to the following items: – Humidity inside the drive –...
Check all power and control cable connections and tighten them if necessary. – Check that all plugs and connectors are tight. 9.4.14. Checking and replacing filter mats Inspection intervals: See the “ACS6080 preventive maintenance schedule” – (3BHS838899 E01). Service during operation: possible. –...
3. Slide the cover up and pull it out of the slots. 4. Turn the cover over and remove the filter mat. 5. Insert the new filter mat and reinstall the ventilation grid. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 200/220...
PREVENTIVE AND CORRECTIVE MAINTENANCE 9.4.15. Testing and replacing auxiliary fan units – Inspection intervals: see the “ACS6080 preventive maintenance schedule” (3BHS838899 E01). Service during operation: possible – – Location: installed behind the doors of the following cabinets: • COU cabinet (2 fan units) •...
3. Disconnect the wires (1) and unscrew (2) the fan units. 4. Remove the fan unit. 5. Reinstall the new one in reverse order of removal. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 202/220...
PREVENTIVE AND CORRECTIVE MAINTENANCE 9.4.16. Testing and replacing air-to-air heat exchangers – Inspection intervals: see the “ACS6080 preventive maintenance schedule” (3BHS838899 E01). Service during operation: not possible – Figure 9-24 Air-to-air heat exchanger overview (type LT-5-5165-UL) 1) Ambient fan 2...
4. Check that the fans run smoothly and if a fan is defective, replace the complete fan unit. 5. Adjust the setting of the thermostat to its original value. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 204/220...
56. 9.4.16.3. Replacing the circuit board 1. Unscrew the front and top cover. 2. Disconnect the ground wire from the front cover (arrow). PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 205/220...
8. Reconnect the ground wire to the front cover. 9. Fasten the covers. 9.4.16.4. Replacing internal fan 1 - left side Procedure 1. Unscrew the front top cover. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 207/220...
Page 208
3. Remove the fan from the housing and unscrew the fan from the mounting bracket. 4. Replace the fan and reassemble the unit in reverse order of removal. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 208/220...
PREVENTIVE AND CORRECTIVE MAINTENANCE 9.4.16.5. Replacing internal fan 2 - right side Procedure 1. Unscrew the front top cover. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 209/220...
Page 210
3. Unscrew the circuit board mounting bracket (1, 2 and 3). 4. Take out the circuit board mounting bracket and place it on the heat exchanger housing. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 210/220...
6. Remove the fan from the housing, and unscrew the fan from the mounting bracket. 7. Replace the fan and reassemble the unit in reverse order of removal. 9.4.16.6. Replacing the ambient fans 1. Unscrew the rear cover. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 211/220...
4. Replace the fan, and reassemble the unit in reverse order of removal. 9.4.17. Replacing the fan unit in an EXU with a DCS880 H4/DCT880 T4 unit Figure 9-26 DCS880 controller - size H4 PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 212/220...
Page 213
NOTE – To identify the miniature circuit breaker, see “Appendix D - Wiring diagrams”. 2. Remove the 6 screws from the fan cover and then remove the fan cover. 3. Unplug the fan cables. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 213/220...
Page 214
CAUTION! To prevent the fan from falling onto you, put a support (ie, a box) underneath. 6. Install the new fan in reverse order of removal. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 214/220...
To identify the miniature circuit breaker, see “Appendix D - Wiring diagrams”. 2. Remove the 6 screws from the fan cover and then remove the fan cover. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 215/220...
Page 216
CAUTION! To prevent the fan from falling onto you, put a support (ie, a box) underneath. 6. Install the new fan in reverse order of removal. PRODUCT DOCUMENT KIND DOCUMENT ID. REV. LANG. PAGE ACS6080 User manual 3BHS842007 E01 216/220...
7. To install the new heat exchanger, proceed in reverse order of removal. For information on adding water to the cooling system, see the manual for the “ACS5000, ACS6000 and ACS6080 water cooling unit WCU800 user manual” (3BHS821937 E01) and “ACS5000, ACS6000 and ACS6080 water cooling unit WCU1400 user manual”...