For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d'aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
INSTALLATIONSMANUAL
Läs denna installationsmanual noga för säkert och korrekt bruk innan luftkonditioneringen installeras.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
Summary of Contents for Mitsubishi Electric PUH-P10MYA
Page 1
Air-Conditioners OUTDOOR UNIT PUH-P8, 10MYA FOR INSTALLER PER L’INSTALLATORE FÜR INSTALLATEURE VOOR DE INSTALLATEUR POUR L’INSTALLATEUR FÖR INSTALLATÖREN PARA EL INSTALADOR PARA O INSTALADOR INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
Page 3
[Fig. 8.2.2] <A> [Ball valve (gas side)] <B> [Ball valve (liquid side)] [Fig. 8.2.3] (This figure shows the valve in the fully open state.) A Valve stem B Stopper pin [Fig. 8.2.1] C Packing (Accessory) D Connecting pipe (Accessory) E Open (Operate slowly) F Cap, copper packing G Service port H Flare nut...
Page 4
[Fig. 9.2.1] (1) Connecting with PEH-P8, 10 (4) Connecting with PEH-P16, 20 PUH-P8, 10 PEH-P16, 20 PUH-P8, 10 PEH-P8, 10 S1 S2 S3 S1 S2 S3 L1 L2 L3 N L1 L2 L3 N S1 S2 S3 OUT OUT IN IN L1 L2 L3 N S1 S2 S3 S1 S2 S3...
Page 5
[Fig. 9.3.1] [Fig. 9.4.1] A When installing conduct from bottom panel B When installing conduct from front panel C Mounting plate (attached) D Knock-out hole...
- The some electric parts should be damaged when power is supplied under of the outdoor unit. the miss wiring. 2. Specifications Model PUH-P8MYA PUH-P10MYA Noise level 56 dB <A> 57 dB <A> Net weight 215 kg 220 kg Maximum refrigerant pressure 3.3 MPa...
4. Space required around unit [Fig. 4.0.1] (P.2) (4) When unit is surrounded by walls <A> Top view <B> Side view Note: <C> When there is little space up to an obstruction • Wall heights (H) of the front and the back sides shall be within overall A Front height of unit.
Caution: 6 You must use one of the following (separately sold) junction pipe sets for the • Use a vacuum pump with a reverse flow check valve. (For R407C models) junction area. - If the vacuum pump does not have a reverse flow check valve, the vacuum Junction-Set Type (multidistributor) pump oil may flow back into the refrigerant cycle and cause deterioration of the refrigerator oil and other trouble.
H Flare nut Caution: [Tightening torque: 120 N·m (1200 kg·cm) • Always remove the connecting pipe from the ball valve and braze it out- Loosen and tighten this nut using a double-ended wrench. side the unit. Coat the flare contact surface with refrigerator oil (Ester oil, ether oil or alkylbenzene [small amount]).] - Brazing the connecting pipe while it is installed will heat the ball valve and cause trouble or gas leakage.
[Fig. 8.4.2] (P.3) 8.4. Thermal insulation of refrigerant piping A Liquid pipe B Gas pipe Electric wire Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas D Finishing tape E Insulater pipe separately with enough thickness heat-resistant polyethylene, so that no gap [Fig.
Example (SW1) [Fig. 9.2.1] (P.4) Operation by switch manipulation Model (1) Connecting with PEH-P8, 10 – – – (2) Free multi-component system 2 Error history clear Clear Ordinary 1 Without heater 3 Refrigerant system 2 With heater address setting Outdoor unit address ↑...
Page 13
Remote controller Error details MELANS display Problem location display Reverse phase, out of phase verification Outdoor unit 4103 Faulty input circuit Outdoor unit 4115 Duplicated M-NET address setting M-NET board 6600 M-NET error in PH/W transmission M-NET board 6602 M-NET bus busy M-NET board 6603 M-NET communication error with P transmission...
10.3. The following occurrences are not problems or errors Remote controller display Problem Cause As a result of the auto vane control operations, during cooling, when downward blowing has been used, after 1 hour has passed horizontal blowing sometimes occurs automati- The auto vane moves on its own.
Page 17
This product is designed and intended for use in the residential, commer- cial and light-industrial environment. The product at hand is • Low Voltage Directive 73/23/EEC based on the following • Electromagnetic Compatibility Directive 89/ EU regulations: 336/EEC Please be sure to put the contact address/telephone number on this manual before handing it to the customer.