Air-Conditioners PEAD-A24,30,36,42AA INSTALLATION MANUAL FOR INSTALLER FOR INSTALLER English For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. MANUEL D’INSTALLATION POUR L’INSTALLATEUR Français Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous...
Page 2
4 300 mm [11-13/16 in] or more E Ceiling surface F Service space (viewed from the side) G Service space (viewed from the direction of arrow) (Unit: mm [in]) Model PEAD-A24, 30AA 1100 [43-5/16] 1154 [45-7/16] 1200 [47-1/4] 1060 [41-23/32] 1200 [47-1/4]...
Page 3
[Fig. 6-1] øB (Unit: mm [in]) øA Model ø15.88 [5/8] ø9.52 [3/8] PEAD-A24, 30, 36, 42AA a Indoor unit b Outdoor unit [Fig. 6-3] [Fig. 6-4] [Fig. 6-5] 90° a Copper tubes c No good e Uneven a Burr c Spare reamer...
Page 4
[Fig. 6-10] Max. 20m [65ft] 1.5-2m [5-7ft] Max. 300mm [11- Correct piping Wrong piping A Insulation (9 mm [3/8 in] or more) B Downward slope (1/100 or more) C Support metal K Air bleeder L Raised M Odor trap Grouped piping D O.
Page 5
[Fig. 7-1] [Fig. 7-2] <A> In case of rear inlet Duct Air inlet Access door Canvas duct Ceiling surface Air outlet Leave distance enough to pre- vent short cycle A Filter <B> In case of bottom inlet B Bottom plate [Fig.
Page 6
[Fig. 8-2-1] [Fig. 8-2-2] A Screw holding cover (1pc) C Terminal box B Cover D Knockout hole E Remove [Fig. 8-2-3] [Fig. 8-2-4] F Use PG bushing to keep the weight of the cable and external force from being applied to N Terminal block for power source and indoor transmission the power supply terminal connector.
Page 7
[Fig. 8-3] A Indoor terminal block A Indoor terminal block 4 Always install an earth wire (1-core 1.5 mm B Earth wire (green/yellow) B Earth wire (green/yellow) [AWG 16]) longer than other cables 5 Remote controller cable C Indoor/outdoor unit connecting wire 3- core 1.5 mm [AWG 16] or more Wire No ×...
Page 8
[Fig. 8-7] Standard 1:1 Indoor/outdoor wiring OC(00) Signal receiving unit wiring A Outdoor unit B Refrigerant address C Indoor unit CN90 D Signal receiving unit [Fig. 8-8] A Signal receiving unit external B Center of Switch box C Switch box D Installation pitch E 6.5 mm (1/4 inch) F 70 mm (2 - 3/4 inch)
Page 9
[Fig. 8-12] Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover. A flat screwdriver whose width of blade is between 4 and 7mm (5/32 - 9/32inch) must be used. [Fig. 8-13] A Thin-wall portion B Bottom case C Remote controller wire D Conducting wire...
Page 11
⁄ Mode number [Fig. 8-21] ⁄ Setting number ⁄ Refrigerant address ⁄ Unit number A Filter button (<Enter> button) B TEST button TEMP. ON/OFF C Set Time button MENU ON/OFF FILTER BACK MONITOR/SET CHECK TEST D Timer On/Off button (Set Day button) PAR-21MAA CLOCK OPERATION...
Page 12
10.1 [Fig. 10-1] A Indoor unit H Refrigerant gas cylinder for R410A with siphon B Union I Refrigerant (liquid) C Liquid pipe J Electronic scale for refrigerant charging D Gas pipe K Charge hose (for R410A) E Stop valve L Gauge manifold valve (for R410A) F Outdoor unit M Service port G Refrigerant gas cylinder operating valve...
Contents 1. Safety precautions ................. 13 9. Test run ....................21 2. Selecting the installation location ............13 10. Maintenance ..................23 3. Selecting an installation site & Accessories ........... 14 4. Fixing hanging bolts ................14 5. Installing the unit ..................14 This Installation Manual describes only for the indoor unit and the connected 6.
3. Selecting an installation site & Accessories • Select a site with sturdy fixed surface sufficiently durable against the weight of unit. Warning: • Before installing unit, the routing to carry in unit to the installation site should be The unit must be securely installed on a structure that can sustain its weight. If determined.
6. Refrigerant piping work 6.1. Refrigerant pipe 6.2.3. Putting nut on [Fig. 6-5] (P.3) [Fig. 6-1] (P.3) a Flare nut a Indoor unit b Copper tube b Outdoor unit • Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube Refer to the Instruction Manual that came with the outdoor unit for the restrictions on having completed burr removal.
6. Refrigerant piping work Refrigerant pipe insulation Tighten the cap to the service port to obtain the initial status. • After connecting refrigerant piping, insulate the joints (flared joints) with thermal insulation tubing as shown below. Retighten the cap [Fig. 6-9] (P.3) A Pipe cover (small) (accessory) Leak test B Caution:...
6. Refrigerant piping work 6.6. Confirming drain discharge 3.Perform the test run in cooling mode, or connect the connector to the ON side of SWE on the Indoor controller board. (The drain pump and the fan are forced to Make sure that the drain-up mechanism operates normally for discharge operate without any remote controller operation.) Make sure using a transparent and that there is no water leakage from the connections.
8. Electrical work 8.1. Power supply [Fig. 8-2-3] (P.6) F Use PG bushing to keep the weight of the cable and external force from being applied to the 8.1.1. Indoor unit power supplied from outdoor unit power supply terminal connector. Use a cable tie to secure the cable. The following connection patterns are available.
8. Electrical work 2) For wireless remote controller [Fig. 8-22] (P.11) 8.5. Function settings (Function selection via the 1. Changing the external static pressure setting. remote controller) 8.5.1 Function setting on the unit (Selecting the unit functions) • Be sure to change the external static pressure setting depending on the duct and 1) For wired remote controller [Fig.
9. Test run 9.1. Before test run 9.2. Test run After completing installation and the wiring and piping of the indoor and outdoor 9.2.1. Using wired remote controller units, check for refrigerant leakage, looseness in the power supply or control 1 Turn on the power at least 12 hours before the test run.
Page 22
9. Test run 4 Press the MODE button B to activate HEAT mode, then check whether warm air 9.3. Test run is blown out from the unit. 9.3.1. Using wireless remote controller (option) 5 Press the FAN button C and check whether fan speed changes. [Fig.
9. Test run On the wireless remote controller with conditions above, following phenomena takes place. • No signals from the remote controller are accepted. • OPE lamp is blinking. • The buzzer makes a short ping sound. Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation) For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
Page 24
Index Consignes de sécurité ................24 Marche d’essai..................32 Choisir l’emplacement de l’installation ............24 10. Entretien ....................34 Sélection de l’emplacement d’installation et accessoires .......25 Fixation des boulons de suspension............25 Installation de l’appareil ................26 Ce Manuel d’installation décrit uniquement l’unité intérieure et l’unité extérieure Mise en place des tuyaux de réfrigérant ..........26 connectée des séries PUHZ.
Page 25
2. Choisir l’emplacement de l’installation • Sites salins. Attention: • Stations thermales. Les emplacements sousmentionnés doivent être évités pour effectuer l’instal- • En présence de gaz sulfurique. lation s’il existe un risque de panne pour le climatiseur. • Autres types de conditions climatiques spéciales. •...
Page 26
5. Installation de l’appareil 5.1. Suspension de l’appareil 5.2. Assurer l’emplacement de l’appareil et fixer les boulons de suspension Apporter l’appareil intérieur emballé sur le lieu de son installation. Pour le suspendre, utiliser une poulie de levage pour le soulever et le faire Utiliser le calibre livré...
Page 27
6. Mise en place des tuyaux de réfrigérant 6.3. Connexion des tuyaux [Fig. 6-8] (P.3) Vérifier le vide avec la soupape multiple de manomètre, puis fermer la soupape • Appliquer une fine couche d’huile de réfrigérant sur la surface du siège de con- multiple de manomètre, et arrêter la pompe à...
Page 28
6. Mise en place des tuyaux de réfrigérant 6.6. Confirmation des décharges d’écoulement 1. Insérer le tuyau d’écoulement (accessoire) dans l’ouverture d’écoulement (marge d’insertion : 25 mm [1 in]).(Ne pas cintrer le tuyau au-delà de 45° pour éviter qu’il Veiller à ce que le mécanisme de décharge d’écoulement fonctionne casse ou se bouche.) normalement et que les raccordements ne présentent aucune fuite.
Page 29
8. Installations électriques 8.1. Alimentation électrique [Fig. 8-2-1] (P.6) Cache-vis (1pc) 8.1.1. Alimentation de l’appareil intérieur provenant de l’appareil Cache extérieur [Fig. 8-2-2] (P.6) Les schémas de connexion suivants sont disponibles. Boîtier à bornes Les schémas d’alimentation de l’appareil extérieur varient selon les modèles. Orifice d’éjection Système 1:1 Retirer...
Page 30
8. Installations électriques 3) Sélection des fonctions (2)Utiliser le cordon de télécommande pour le brancher au connecteur (CN90) Si deux télécommandes sont connectées, réglez l’une sur “principal” et l’autre sur sur la carte du circuit de commande de l’appareil intérieur. “auxiliaire”.
Page 31
8. Installations électriques 8.5. Réglage des fonctions (Sélection des fonctions numéro d’appareil 01. Pour spécifier chaque appareil intérieur parmi deux, trois ou quatre appareils inté- par la télécommande) rieurs raccordés, lorsque ces appareils fonctionnent ensemble, sélectionner un 8.5.1. Réglage des fonctions sur l’appareil (Sélection des fonctions numéro d’appareil 01 à...
Page 32
9. Marche d’essai 9.1. Avant la marche d’essai 9.2. Marche d’essai Lorsque l’installation, le tuyautage et le câblage des appareils intérieur et 9.2.1. Utilisation de la télécommande filaire extérieur sont terminés, vérifier l’absence de fuites de réfrigérant, la Mettre l’appareil sous tension au moins 12 heures avant l’essai de fonctionnement. fixation des câbles d’alimentation et de commande, l’absence d’erreur de Appuyer deux fois sur la touche [TEST] (ESSAI).
Page 33
9. Marche d’essai 9.3. Marche d’essai Remarque : • Dirigez la télécommande vers le récepteur de l’appareil intérieur tout en 9.3.1. Utilisation de la télécommande sans fil (facultatif) effectuant les étapes à [Fig. 9-3] (P.11) • Il n’est pas possible d’utiliser le mode FAN (ventilation), DRY (déshumidifica- Mettez l’appareil sous tension au moins 12 heures avant la marche d’essai.
9. Marche d’essai • Si l’appareil ne fonctionne pas correctement après la marche d’essai ci-dessus, reportez-vous au tableau suivant pour résoudre le problème. Symptôme Cause Télécommande sans fil LED 1, 2 (CCI de l’appareil extérieur) Pendant les 2 minutes Après l’éclairage de la LED 1, 2, la LED 2 •...
Page 36
This product is designed and intended for use in the residential, commercial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN KB79P514H01...