Revision: MSZ-G09SV - and MSZ-G12SV - have been added. MICROPROCESSOR CONTROL, SERVICE FUNCTIONS, and PARTS LIST have been partially modified. Please void OB245. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS No. OB245 REVISED EDITION-A SERVICE MANUAL Wireless type Models MSZ-G09SV - MUZ-G09SV - ( WH ) MSZ-G09SV - MUZ-G09SV -...
TECHNICAL CHANGES MSZ-G09SV - MSZ-G09SV - MSZ-G12SV - MSZ-G12SV - 1. Remote controller has been changed. MUZ-G09SV - MUZ-G09SV - MUZ-G12SV - MUZ-G12SV - 1. Only model name has changed. PART NAMES AND FUNCTIONS MSZ-G09SV- MSZ-G12SV- MSZ-G09SV- MSZ-G12SV- INDOOR UNIT Grille Air cleaning filter(white bellows...
MUZ-G09SV- MUZ-G12SV- MUZ-G09SV- MUZ-G12SV- OUTDOOR UNIT Air inlet Piping Drain hose Air outlet Drain outlet MSZ-G09SV- MSZ-G12SV- REMOTE CONTROLLER Signal transmitting section Operation display section CLOCK 6 00 1 1 00 OPERATE /STOP (ON /OFF)button ON/OFF COOL WARM OPERATION SELECT button TEMPERATURE buttons MODE I FEEL COOL DRY HEAT...
Page 4
MSZ-G09SV- MSZ-G12SV- Signal transmitting section Operation display section CLOCK AMPM AMPM OPERATE /STOP (ON /OFF)button ON/OFF WARM COOL TEMPERATURE buttons Open the front lid. CLOCK AMPM ON/OFF WARM COOL VANE control button FAN SPEED CONTROL button STOP I FEEL COOL OFF-TIMER button VANE START...
Specifications and rating conditions of main electric parts INDOOR UNIT MSZ-G09SV - MSZ-G12SV - Model Item MSZ-G09SV - MSZ-G12SV - 1.5+ 440V Indoor fan capacitor (C11) 250V 3.15A Fuse (F11) 93:5A 250V Thermal fuse (F12) MP20GA 12V 300" Vane motor (MV1, MV2) ERZV10D471 Varistor...
NOISE CRITERIA CURVES MSZ-G09SV- MUZ-G09SV- MSZ-G09SV- MUZ-G09SV- SPEED SPL(dB(A)) LINE SPEED SPL(dB(A)) LINE FUNCTION FUNCTION COOLING COOLING High High HEATING HEATING Test conditions, Test conditions, Cooling : DB 27: WB 19: Cooling : DB 35: WB (24:) Heating : DB 20: WB 15: Heating : DB 7: WB 6: NC-70 NC-70...
OUTLINES AND DIMENSIONS Unit: mm MSZ-G09SV- INDOOR UNIT Installation plate Indoor unit 81.5 116.5 Wall hole [65 Installation plate Liquid line [6.35-0.5m Gas line [9.52-0.43m Air in Insulation [37 O.D. [21 I.D. Drain hose [16 (Connected part O.D.) 17.5 Insulation [28 Air out Power supply cord Lead to right 1.0m...
Page 9
Unit: mm MSZ-G09SV- INDOOR UNIT Installation plate Indoor unit 81.5 116.5 Wall hole [65 Installation plate Liquid line [6.35-0.5m Gas line [9.52-0.43m Air in Insulation [37 O.D. [21 I.D. Drain hose [16 (Connected part O.D.) Insulation [28 Air out Power supply cord Lead to right 1.0m Lead to left 0.3m...
Page 10
MUZ-G09SV- MUZ-G12SV- Unit: mm MUZ-G09SV- MUZ-G12SV- OUTDOOR UNIT REQUIRED SPACE Even if the right/ left sides or back side are vacant, the top has to be at least 100mm unobstructed. Drainage holes [28 Air in Drainage holes [28 However, either the left/ right sides or back side should be unobstructed.
PERFORMANCE CURVES MSZ-G09SV- MSZ-G09SV- MSZ-G12SV- MSZ-G12SV- MUZ-G09SV- MUZ-G09SV- MUZ-G12SV- MUZ-G12SV- The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
Page 17
Cooling capacity These values are under rated (frequency). 11.5 11.6 10.5 10.6 MUZ-G09SV - MUZ-G09SV - MUZ-G09SV - MUZ-G09SV - Correction of Cooling capacity Correction of total input 150(Hz) 150(Hz) The operational frequency of compressor The operational frequency of compressor MUZ-G12SV - MUZ-G12SV - MUZ-G12SV -...
Page 18
Heating capacity NOTE:The following curves are for the heating operation without any frost. These values are under rated (frequency). 28.0 29.3 25.9 27.1 23.7 24.8 21.6 22.6 19.4 20.3 17.2 18.1 15.1 15.8 12.9 13.5 MUZ-G09SV - MUZ-G09SV - MUZ-G09SV - MUZ-G09SV - Correction of Heating capacity Correction of total input...
Page 19
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT How to operate with fixed operational frequency of the compressor. 1. Press the EMERGENCY OPERATION switch on the front of the indoor unit , and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner. 2.
MICROPROCESSOR CONTROL MSZ-G09SV- MSZ-G09SV- MSZ-G12SV- MSZ-G12SV- MUZ-G09SV- MUZ-G09SV- MUZ-G12SV- MUZ-G12SV- WIRELESS REMOTE CONTROLLER MSZ-G09SV- MSZ-G09SV- MSZ-G12SV- MSZ-G12SV- Signal transmitting section Signal transmitting section Operation display section CLOCK AMPM AMPM OPERATE /STOP Operation display section (ON /OFF)button ON/OFF WARM COOL CLOCK 6 00 1 1 00 TEMPERATURE buttons OPERATE /STOP...
Page 27
Once the mode is fixed, the mode does not change by room temperature afterwards. Under the ON-TIMER ( ) operation, mode is determined according to the room temperature at set time the opera- tion starts. When the system is stopped on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” ( ) mode, the system operates in previous mode automatically regardless of the room temperature.
Page 28
5. TEMPERATURE buttons In “I FEEL CONTROL” (h )mode, set temperature is decided by the microprocessor based on the room temperature. In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is speed, the indoor unit receives the signal emits a beep tone.
Page 29
8-1-2. DRY mode of “I FEEL CONTROL” The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room temperature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease. 1.
Page 30
(3) Warm air control. When the following any condition of 1 (a. ~ d.) and the condition of 2 are satisfied at the same time, warm air control works. 1 a.) when the operation mode has been changed to HEAT mode b.) when cold air prevention has been released c.) when defrosting has been finished d.) when the compressor starts in HEAT mode...
Page 31
Time chart of defrosting in HEAT mode (reverse type) <indoor unit> horizontal set position set position Horizontal vane Indoor fan set speed Very Low (temperature of indoor coil thermistor > 18:) seconds <outdoor unit> MAX. 105Hz (MSZ-G09SV) MAX. Hz MAX. 125Hz (MSZ-G12SV) MAX.
Page 32
9-4. HEAT ( ) OPERATION (1) Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select HEAT mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 16 ~ 31°C.
Page 33
(5) Dew prevention During COOL or DRY operation with the vane angle at Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention. (6) SWING MODE ( By pressing the SWING button, vertical vane swings horizontally.
Page 34
(9) ECONO COOL ( ) operation (ECONOmical operation) When the ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(RT12). SWING operation makes you feel cooler than set temperature.
Page 35
PROGRAM TIMER MSZ-G09SV- MSZ-G12SV- MSZ-G09SV- MSZ-G12SV- The OFF timer and ON timer can be used in combination. “ ” or “ ” and “ ” or “ ” display shows the order of the OFF timer and ON timer operation. (Example 2) The current time is 11:00 AM.
Page 36
9-9. Operational frequency control of outdoor unit 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set temper- ature. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection, electric current protection and overload protection and also by the maximum/minimum frequency.
Page 37
9-10. Expansion valve control (LEV control) (1) Outline of LEV control The LEV basic control is comprised of setting LEV opening degree to the standard opening degrees set for each opera- tional frequency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air conditioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge temper- ature (Shell temperature) of the compressor, developing the unit’s performance.
Page 38
(2) Time chart Air conditioner ON Air conditioner OFF Positioning (thermostat off) Opening degree is corrected according to discharge Standard Commanded temperature. opening to open degree Time 13 min. OFF Time (3) Control data (a) Reference value of target discharge temperature (COOL/HEAT :) MSZ-G09SV 58/49...
Page 39
9-11. Outdoor fan motor control The AC fan motor turns ON/OFF, interlocking with the compressor. [ON] The AC fan motor turns ON 5 seconds before the compressor starts up. [OFF] The AC fan motor turns OFF 15 seconds after the compressor has stopped running. 5 sec.
Page 40
9-13. Indoor fan motor control The detected rotational frequency of the indoor fan motor (AC fan motor) is feeded-back to the microprocessor and then the microprocessor works to keep the rotational frequency at a fixed value against load fluctuation. (1) Circuit block diagram Solid state relay output every 100Hz pulse output...
SERVICE FUNCTIONS MSZ-G09SV - MSZ-G12SV - MSZ-G09SV - MSZ-G12SV - 10-1. CHANGE IN DEFROST SETTING <JS> When the JS wire of the outdoor electronic control P.C. board is cut, the defrost temperature will be changed. (Refer to page 59.) Jumper wire Change point Deforst finish temperature changes from 13: to 15:.
Page 42
(2) How to modify the remote controller P.C. board <MSZ-G09/12SV- > Remove batteries before modification. The board has a print as shown below : NOTE : For remodelling, take out the bat- teries and press the OPERATE/STOP(ON/OFF)button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
Page 43
10-4. AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment the power has restored after power failure.
TROUBLESHOOTING MSZ-G09SV - MSZ-G12SV - MSZ-G09SV - MSZ-G12SV - 11-1. Cautions on troubleshooting 1. Before troubleshooting, check the following: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 2. Take care the following during servicing. 1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after con- firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
Page 45
11-2. Troubleshooting procedure The following procedure facilitates identifying defective points. Details of OPERATION INDICATOR lamp flashing are located on page 42 and 43. Start Indoor unit Indoor unit OPERATION INDICATOR operates. does'nt receive lamp on the indoor unit is Outdoor unit the signal from flashing on and off.
Page 46
1. Troubleshooting check table (Indoor unit troubleshooting check table) MSZ-G09SV - MSZ-G12SV - MSZ-G09SV - MSZ-G12SV - flashing Operation Indicator · Flashing of the operation indicator lamp (on the left-hand side) indicates possible abnormalities. · The operation indicator lamp (on the left-hand side) is lighted during normal operation. Symptom Operation indicator lamp Abnormal point...
Page 47
(Outdoor LED indication table) <Outdoor electronic control P.C. board> MUZ-G09SV - MUZ-G12SV - MUZ-G09SV - MUZ-G12SV - NOTE 1. The location of LED is illustrated at the right figure. Transistor Hybrid 2. LED lights up during normal operation. module flashing transformer Symptom LED indication...
Page 48
2. Checking mis-wiring and serial signal error Outdoor unit does not operate. When the OPERATION INDICATOR lamp (on the left-hand side) flashes on and off continuously or only once. 1. Turn OFF the power supply. 2. Turn ON the power supply. 3.
Page 49
3. Trouble shooting procedure of main parts (Simple check method of main parts) MSZ-G09SV - MSZ-G12SV - MUZ-G09SV - MUZ-G12SV - MSZ-G09SV - MSZ-G12SV - MUZ-G09SV - MUZ-G12SV - Part name Checking method and criterion Room tempera- Disconnect the connector and measure the resistance with a tester. ture thermistor (Part temperature : 10:~30:) (RT11)
Page 50
Part name Checking method and criterion Outdoor fan Measure the resistance between the terminals with a tester. motor (MF61) (Part temperature : -10:~40:) Normal abnormal MUZ-G09SV MUZ-G12SV WHT-BLK 246"~301" 177"~217" Open or short circuit BLK-RED 174"~214" 308"~378" Measure the resistance between the terminals with a tester. Vane motor (Part temperature : 10:~30:) (MV1, MV2)
Page 51
How to check inverter/ compressor Disconnect the connector between compressor and transistor module. Check the voltage See B 'Check of open phase' on page 51. between terminals. Are voltages Check the resistance of transistor module. See C 'Check of transistor module' on page 51. balanced? Replace the outdoor Is resistance...
Page 52
Check of compressor Start E 'Check of compressor Replace the compressor. winding' on page 48. Is compressor normal? F 'Check of compressor Is the compressor operation time' on page operation time more than Replace the compressor. 48. Does the compressor 10 seconds? operate continuously? Check the refrigerant circuit.
Page 53
(How to check main parts) Check of indoor fan motor. Indoor fan does not operate. Replace the indoor fan motor. Yes(0 or ∞) Disconnect lead wires from CN 211 on indoor electronic Turn OFF the control P.C. board. Is resistance power supply and Measure resistance 0"(short circuit) or...
Page 54
Check of indoor electronic control P.C. board The unit does not operate with the remote controller. The OPERATION INDICATOR lamp does not light up either, with the EMERGENCY OPERATION switch ON. Check both “parts side” Turn OFF the power supply. and “pattern side”...
Page 55
Check of R.V. coil Cooling operates when heating is expected. First, measure resistance of the R.V. coil to check if it is defective or not. If the connector CN 721 is not connected or the R.V. coil is open, the voltage occurs between the terminals even when the control is OFF.
Page 56
(How to check power supply and others) Check of power supply Inverter does not work. Outdoor terminal block Disconnect the connector between compressor and In-out transistor module. connecting Turn ON power supply to indoor wire unit and press EMERGENCY Repair wiring. OPERATION switch.
Page 57
Check of expansion valve (LEV) Heating/ Cooling do not operate. 1Press the EMERGENCY OPERATION switch. 2Turn OFF the power supply. 3Turn ON the power supply. With remote controller set toward the indoor unit, press OPERATE/ STOP(ON/ OFF) button and confirm one beep tone. LEV operates in full-opening direction.
Page 58
TEST POINT DIAGRAM AND VOLTAGE MSZ-G09SV - MSZ-G12SV - MSZ-G09SV - MSZ-G12SV - Indoor electronic control P.C. board Varistor (NR11) Fuse (F11) 250V AC 3.15A Fan motor power supply Power supply input 230V AC Room temperature thermistor (RT11) Timer short mode point (JPG, JPS) (Refer to page 44.)
Page 59
MUZ-G09SV - MUZ-G12SV - MUZ-G09SV - MUZ-G12SV - Outdoor electronic control P.C. board Defrost thermistor(RT61) Fin temperature thermistor(RT64) Discharge temperature thermistor(RT62) 90 100 110 120 10 20 30 40 50 60 70 80 Temperature(:) Temperature(:) Temperature(:) Discharge Defrost temperature temperature connector monitor thermistor...
Page 60
MUZ-G09SV - MUZ-G09SV - Current -limit- Noise filter P.C. board ing relay (X64) Surge absorber (DSA61) Varistor (NR61) 230V AC MUZ-G12SV - MUZ-G12SV - Noise filter P.C. board Current -limit- ing relay (X64) Surge absorber (DSA61) Varistor (NR61) 230V AC...
Page 61
MUZ-G09SV - MUZ-G12SV - MUZ-G09SV - MUZ-G12SV - Relay P.C. board R.V. coil(21S4) 230V AC Outdoor fan motor (MF61) 230V AC...
DISASSEMBLY INSTRUCTIONS <"Terminal with lock mechanism" Detaching points> In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
OPERATING PROCEDURE PHOTOS 3. Removing the electrical box Screw of the ground wire Photo 3 (1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (Refer to 2) (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211 and CN121) and the vane motor connector (CN151) on the electronic control P.C.
Page 64
12-2. MUZ-G09SV - MUZ-G12SV - MUZ-G09SV - MUZ-G12SV - OUTDOOR UNIT OPERATING PROCEDURE PHOTOS 1. Removing the cabinet Screws of the Photo 1 top panel (1) Remove the screws fixing the service panel. Screws (2) Pull down the service panel and remove it from the cabinet. of the (3) Remove the screws fixing the cabinet and top panel.
Page 65
OPERATING PROCEDURE PHOTOS 6. Removing the outdoor fan motor Photo 5 (1) Remove the service panel, top panel and the cabinet. (Refer to 1) Set screws of the (2) Disconnect the connector remove the clamp of fan motor outdoor fan motor Lead clamps lead wire.
PARTS LIST MSZ-G09SV - (WH) MSZ-G12SV - (WH) MSZ-G09SV - (WH) MSZ-G12SV - (WH) 13-2. INDOOR UNIT HEAT EXCHANGER 13-1. INDOOR UNIT STRUCTURAL PARTS 12 (w) SCREW CATCH 7 (w) (w) These figures show about MSZ-G12SV. 13-1. INDOOR UNIT STRUCTURAL PARTS Symbol Q'ty/unit in Wiring...
Page 67
MSZ-G09SV - (WH) MSZ-G12SV - (WH) MSZ-G09SV - (WH) MSZ-G12SV - (WH) 13-4. ACCESSORY AND 13-3. INDOOR UNIT FUNCTIONAL PARTS AND REMOTE CONTROLLER PART ELECTRICAL PARTS SLEEVE BEARING ROOM TEMPERATURE THERMISTOR MSZ-G09/12SV- MSZ-G09/12SV- FUSE VARISTOR 13-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS Part numbers that are circled are not shown in the illustration.
Page 68
MUZ-G09SV - MUZ-G12SV - MUZ-G09SV - MUZ-G12SV - 13-5. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Symbol Q'ty/unit in Wiring Part No. Part Name Remarks MUZ-G09SV- MUZ-G12SV- Diagram TOP PANEL M21 32E 297 M21 21G 297 TOP PANEL...
MUZ-G09SV - MUZ-G12SV - MUZ-G09SV - MUZ-G12SV - 13-6. OUTDOOR UNIT ELECTRICAL PARTS Part numbers that are circled are not shown in the illustration. Symbol Q'ty/unit in Wiring Part No. Part Name Remarks MUZ-G09SV- MUZ-G12SV- Diagram T2W E66 357 SMOOTHING CAPACITOR 1500+/420V SMOOTHING CAPACITOR T2W E68 357...
OPTIONAL PARTS 14-1. AIR CLEANING FILTER AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity. Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible. Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
Page 72
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN C C Copyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD New publication, effective Mar. 2001 Specifications subject to change without notice. Distributed in Mar. 2001 No. OB245 REVISED EDITION A 249 Issued in. Mar. 2000 No. OB245 249...