1. Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. • Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. •...
Page 4
19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.). 20.
2. Specification Indoor CS-E12JKKW-1 Model Outdoor CU-E12JKK-1 Performance Test Condition Phase, Hz Single, 60 Power Supply Min. Mid. Max. Min. Mid. Max. 1.20 3.48 3.85 1.20 3.48 3.85 Capacity BTU/h 4100 11900 13100 4100 11900 13100 Running Current Input Power 1.15k...
Page 6
Type Propeller Material Motor Type Induction (6 poles) Input Power Output Power Speed 760 - 840 Moisture Removal L/h (Pt/h) 1.1 (2.3) Cooling : 6.0 (210) /min (ft /min) Heating : 9.2 (323) Cooling : 7.5 (264) /min (ft /min) Heating : 10.1 (355) Cooling : 9.7 (345) Indoor Airflow...
Page 7
DRY BULB WET BULB Maximum 89.6 73.4 Indoor Operation Range (Cooling) Minimum 60.8 51.8 Maximum 109.4 78.8 Outdoor Operation Range (Cooling) Minimum 60.8 51.8 Maximum 86.0 Indoor Operation Range (Heating) Minimum 60.8 Maximum 75.2 64.4 Outdoor Operation Range (Heating) Minimum Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F...
Page 8
Indoor CS-E18JKK-1 Model Outdoor CU-E18JKK-1 Performance Test Condition Phase, Hz Single, 60 Power Supply Min. Mid. Max. Min. Mid. Max. 1.30 5.01 5.80 1.30 5.01 5.80 Capacity BTU/h 4400 17100 19800 4400 17100 19800 Running Current Input Power 1.30k 1.85k 1.30k 1.85k 5.20...
Page 9
Type Propeller Material Motor Type Induction (8 poles) Input Power Output Power Speed 500 - 550 Moisture Removal L/h (Pt/h) 1.7 (3.6) Cooling : 12.5 (441) /min (ft /min) Heating : 13.6 (479) Cooling : 13.7 (485) /min (ft /min) Heating : 14.8 (526) Cooling : 16.0 (565) Indoor Airflow...
Page 10
DRY BULB WET BULB Maximum 89.6 73.4 Indoor Operation Range (Cooling) Minimum 60.8 51.8 Maximum 109.4 78.8 Outdoor Operation Range (Cooling) Minimum 60.8 51.8 Maximum 86.0 Indoor Operation Range (Heating) Minimum 60.8 Maximum 75.2 64.4 Outdoor Operation Range (Heating) Minimum Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB) Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F...
3. Features • Inverter Technology Wider output power range Energy saving Quick Cooling More precise temperature control • Environment Protection Non-ozone depletion substances refrigerant (R410A) • Long Installation Piping CS/CU-E12JK-1, long piping up to 49.2 ft CS/CU-E18JK-1, long piping up to 65.6 ft •...
11. Installation Instruction 11.1 E12JKKW-1 11.1.1 Select the Best Location 11.1.2 Indoor/Outdoor Unit Installation Diagram 11.1.1.1 Indoor Unit • Do not install the unit in excessive oil fume areas such as kitchens, workshops and etc. • There should not be any heat source or steam near the unit.
Page 33
11.1.3 Indoor Unit 11.1.3.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent if from the vibration. The centre of installation plate should be at more than at right and left of the wall. The distance from installation plate edge to ceiling should more than From installation plate left edge to unit’s left side is From installation plate right edge to unit’s right side is...
Page 34
11.1.3.3 Indoor Unit Installation 11.1.3.4 For the right rear piping 11.1.3.5 For the right bottom piping 11.1.3.6 For the embedded piping (This can be used for left rear piping and bottom piping also.)
Page 35
11.1.3.7 Connect the Cable to the Indoor Unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Unscrew the conduit cover and fix the conduit connector to conduit cover with lock nut, then secure it against chassis.
Page 36
11.1.3.8 Wiring Stripping and connecting requirement 11.1.3.9 Cutting and flaring the piping Please cut using pipe cutter and then remove the burrs. Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe.
11.1.4 Outdoor Unit 11.1.4.1 Install the Outdoor Unit • After selecting the best location, start installation according to indoor/outdoor unit installation diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø13/32’’). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
Page 38
11.1.4.2.4 Gas Leak Checking Pressure test to system to 400 PSIG with dry nitrogen, in stages. Thoroughly leak check the system. If the pressure holds, release the nitrogen and proceed to section 4. 11.1.4.2.5 Evacuation of the equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedures.
Page 39
8. Connect the power cord and connecting wire between indoor unit and outdoor unit according to the diagram below. 9. Secure the wire onto the control board with the holder (clamper). 10. After completing wiring connections, reattach the control board cover (Metal and Resin) and the top panel to the original position with the screws.
11.2 E18JKK-1 11.2.1 Select the Best Location 11.2.2 Indoor/Outdoor Unit Installation Diagram 11.2.1.1 Indoor Unit • Do not install the unit in excessive oil fume areas such as kitchens, workshops and etc. • There should not be any heat source or steam near the unit.
Page 41
11.2.3 Indoor Unit 11.2.3.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent if from the vibration. The centre of installation plate should be at more than at right and left of the wall. The distance from installation plate edge to ceiling should more than From installation plate left edge to unit’s left side is From installation plate right edge to unit’s right side is...
Page 42
11.2.3.3 Indoor Unit Installation 11.2.3.4 For the right rear piping 11.2.3.5 For the right bottom piping 11.2.3.6 For the embedded piping (This can be used for left rear piping and bottom piping also.)
Page 43
11.2.3.7 Connect the Cable to the Indoor Unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Unscrew the conduit cover and fix the conduit connector to conduit cover with lock nut, then secure it against chassis.
Page 44
11.2.3.8 Wiring Stripping and connecting requirement 11.2.3.9 Cutting and flaring the piping Please cut using pipe cutter and then remove the burrs. Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe.
Page 45
11.2.4 Outdoor Unit 11.2.4.1 Install the Outdoor Unit • After selecting the best location, start installation according to indoor/outdoor unit installation diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø13/32’’). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.
11.2.4.3 Evacuation of the equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedures. 1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
Page 47
9. Secure the wire onto the control board with the holder (clamper). 10. After completing wiring connections, reattach the particular plate control board cover (Metal and Resin) and the original position with the screws. 11. For wire stripping and connection requirement, refer to instruction of indoor unit.
12. Operation Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operation mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
12.1.3.2 Thermostat control (E18JKK-1) • Compressor is OFF when Intake Temperature - Internal Setting Temperature < 28.4°F. • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF point. 12.1.4 Heating Operation 12.1.4.1 Thermostat control...
• Auto Fan Speed [Cooling, Dry] According to room temperature and setting temperature, indoor fan speed is determined automatically. The indoor fan will operate according to pattern below. During operation, indoor fan motor may stop due to odor prevention. [Heating] According to indoor pipe temperature, automatic heating fan speed is determined as follows.
12.5 Airflow Direction • There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes). • Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).
12.5.3 Horizontal Airflow 12.5.3.1 E12JKK-1 The horizontal airflow direction louvers can be adjusted manually by hand. 12.5.3.2 E18JKK-1 • Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below.
When quiet operation is stopped, operation is shifted to normal operation with previous setting. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode. During quiet operation, if ON timer activates, quiet operation maintains.
12.9 Timer Control 12.9.1 ON Timer Control • ON Timer can be set using remote control, where the unit with timer set will start operation earlier than the setting time. This is to provide a comfortable environment when reaching the set ON time. •...
13. Operation Control (For Multi Split Connection) During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in this chapter. 13.1 Cooling operation 13.1.1 Thermostat control • Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting temperature <...
13.4 Automatic Operation • This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode, indoor intake and outdoor air temperature. • During operation mode judgment, indoor fan motor (with speed of -Lo) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature.
Protection Control 14.1 Protection Control For All Operations 14.1.1 Restart Control (Time Delay Safety Control) • The compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. •...
Page 58
If the set value exceeds again within 30 seconds after the compressor starts, the operation will restart after 1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer LED will be blinking (“F99” is indicated). 14.1.4.2 E18JK-1 •...
14.1.7 Low Pressure Protection Control (Gas Leakage Detection) (For E12JK-1 only) • Control start conditions For 5 minutes, the compressor continuously operates and outdoor total current is between 0.66A and 1.25A (Cooling), 0.66A and 2.65A (Heating) During Cooling and Soft Dry operation: Indoor suction temperature –...
14.2.2 Cooling Overload Control • Pipe temperature limitation / restriction. Detects the outdoor pipe temperature and carry out restriction / limitation below (Limit the compressor operation frequency) The compressor stops if outdoor pipe temperature exceeds 141.8°F. (For E12JK-1 only) The compressor stops if outdoor pipe temperature exceeds 145.4°F. (For E18JK-1 only) If the compressor stops 4 times in 20 minutes, Timer LED blinks (“F95”...
Page 61
14.2.6.3 Overload Protection Control • The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown below. • If the heat exchanger temperature exceeds 140°F, compressor will stop. 14.2.6.4 Low Temperature Compressor Oil Return Control • In heating operation, if the outdoor temperature falls below 14°F when compressor starts, the compressor frequency will be regulated up to 600 seconds.
15. Servicing Mode 15.1 Auto Off/On Button AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunction. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds.
Press Auto OFF/ON button to toggle remote control receiving sound. - Short “beep”: Turn OFF remote control receiving sound. - Long “beep”: Turn ON remote control receiving sound. After Auto OFF/ON button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON Mode is restarted.
16. Troubleshooting Guide 16.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air Temperature Such problems include insufficient insulation, problem with the (kg/cm (°F) power source, malfunction of a compressor and a fan.
Page 65
16.1.1 Relationship between the condition of the air conditioner and pressure and electric current • Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
16.2 Breakdown Self Diagnosis Function 16.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code) • Once error occurred during operation, the unit will stop its operation, and Timer LED blinks. • Although Timer LED goes off when power supply is turned off, if the unit is operated under a breakdown condition, the LED will ON again.
Page 68
Note: “○” – Frequency measured and fan speed fixed The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the CHECK button at remote control. Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit.
16.4 Self-diagnosis Method 16.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions • During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused • Faulty indoor unit PCB.
Page 70
16.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions • During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused • Wrong models interconnected. • Wrong indoor unit or outdoor unit PCBs mounted. •...
Page 71
16.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. •...
Page 72
16.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. • Faulty sensor.
Page 73
16.4.5 H16 (Outdoor Current Transformer Open Circuit) Malfunction Decision Conditions • A current transformer (CT) is detected by checking the compressor running frequency (≥ rated frequency) and CT detected input current (less than 0.65A) for continuously 20 seconds. Malfunction Caused •...
Page 74
16.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions • The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm) Malfunction Caused •...
Page 75
16.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. •...
Page 76
16.4.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. •...
Page 77
16.4.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. •...
Page 78
16.4.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. •...
Page 79
16.4.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection.
Page 80
16.4.12 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions • The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused • Wrong models interconnected. • Wrong indoor unit and outdoor unit PCBs used. • Indoor unit or outdoor unit PCB defective.
Page 81
16.4.13 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. •...
Page 82
16.4.14 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors. Malfunction Caused • Faulty connector connection. •...
Page 83
16.4.15 H58 (Patrol Sensor Abnormality) Malfunction Decision Conditions • If Patrol sensor feedback is 0V or 5V continuous for 6 hours. • Error will display only when the Patrol operation is ON. Malfunction Caused • Faulty connector connection. • Faulty Patrol sensor. Troubleshooting...
Page 84
16.4.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions • The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused • Operation stops due to short circuit inside the fan motor winding. •...
Page 85
16.4.17 H98 (Indoor High Pressure Protection) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions • During heating operation, the temperature detected by the indoor pipe temperature sensor is above 140°F. Malfunction Caused •...
Page 86
16.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Malfunction Decision Conditions • Freeze prevention control takes place (when indoor pipe temperature is lower than 35.6°F) Malfunction Caused • Clogged air filter of the indoor unit • Dust accumulation on the indoor unit heat exchanger •...
Page 87
16.4.19 F11 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • When cooling operation, when indoor pipe temperature or indoor heat exchanger temperature sensor is above 113°F. Malfunction Caused • Faulty connector connection. • Faulty indoor pipe temperature sensor. • Faulty indoor main PCB.
Page 88
16.4.20 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions • When the different between indoor intake air temperature and indoor pipe temperature is above 50°F or indoor pipe temperature is below 30.2°F Remark: When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit(s).
Page 89
16.4.21 F90 (Power Factor Correction Protection) Malfunction Decision Conditions • During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level. Malfunction Caused • DC voltage peak due to power supply surge.
Page 90
16.4.22 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions • During cooling, compressor frequency = Fcmax. • During cooling and heating operation, running current: 0.65A < I < 1.65A. • During cooling, indoor intake - indoor pipe < 39.2°F. Malfunction Caused •...
Page 91
16.4.23 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused • Compressor terminal disconnect • Outdoor PCB malfunction Troubleshooting...
Page 92
16.4.24 F95 (Cooling High Pressure Abnormality) Malfunction Decision Conditions During operation of cooling, when outdoor unit heat exchanger high temperature data (141.8°F) is detected by the outdoor pipe temperature sensor. Malfunction Caused • Outdoor pipe temperature rise due to short circuit of hot discharge air flow. •...
Page 93
16.4.25 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (212°F) is detected by the IPM temperature sensor. Malfunction Caused • IPM overheats due to short circuit of hot discharge air flow. • IPM overheats due to defective of outdoor fan motor.
Page 94
16.4.26 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature data (233.6°F) is detected by the compressor tank temperature sensor. Malfunction Caused • Refrigerant shortage (refrigerant leakage). • 2/3 way valve closed. • Detection error due to faulty compressor tank temperature sensor.
Page 95
16.4.27 F98 (Input Over Current Detection) Malfunction Decision Conditions During cooling and heating operation, when an input over-current (16.8A) is detected by checking the input current value being detected by current transformer (CT) with the compressor running. Malfunction Caused • Over-current due to compressor failure.
16.4.28 F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an output over-current (18.5A) is detected by checking the current that flows in the inverter DC peak sensing circuitry. Malfunction Caused • DC peak due to compressor failure. •...
17. Disassembly and Assembly Instructions WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 17.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 17.1.1...
19. Exploded View and Replacement Parts List 19.1 Indoor Unit 19.1.1 CS-E12JKKW-1 Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 110
REF. NO. PART NAME & DESCRIPTION QTY. CS-E12JKKW-1 REMARK CHASSY COMPLETE CWD50C1633 FAN MOTOR L6CBYYYL0055 CROSS FLOW FAN COMPLETE CWH02C1076 BEARING ASSY CWH64K007 SCREW - CROSS FLOW FAN CWH551146 EVAPORATOR CO. CWB30C3116 FLARE NUT (LIQUID) CWT251030 FLARE NUT (GAS) CWT251032...
Page 111
19.1.2 CS-E18JKK-1 Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 112
REF. NO. PART NAME & DESCRIPTION QTY. CS-E18JKK-1 REMARK CHASSY COMPLETE CWD50C1637 FAN MOTOR L6CBYYYL0056 CROSS FLOW FAN COMPLETE CWH02C1077 BEARING ASS’Y CWH64K007 SCREW - CROSS FLOW FAN CWH551146 EVAPORATOR CWB30C3118 FLARE NUT (LIQUID) CWT251030 FLARE NUT (GAS) CWT251032 HOLDER SENSOR CWH32143 CONTROL BOARD CASING CWH102370A...
19.2 Outdoor Unit 19.2.1 CU-E12JKK-1 Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 114
REF. NO. PART NAME & DESCRIPTION QTY. CU-E12JKK-1 REMARK CHASSY ASS’Y CWD50K2081A FAN MOTOR BRACKET CWD541030 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR CWA951466 SCREW - FAN MOTOR MOUNT CWH55406J PROPELLER FAN ASS’Y CWH03K1010 NUT - PROPELLER FAN CWH56053J COMPRESSOR 5RS102XBC01 ANTI - VIBRATION BUSHING...
Page 115
19.2.2 CU-E18JKK-1 Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 116
REF. NO. PART NAME & DESCRIPTION QTY. CU-E18JKK-1 REMARK CHASSY ASS’Y CWD52K1226A ANTI-VIBRATION BUSHING CWH50077 COMPRESSOR 5CS130XAD04 NUT-COMPRESSOR MOUNT CWH56000J FAN MOTOR BRACKET CWD541126 FAN MOTOR CWA951686 SCREW - FAN MOTOR BRACKET CWH551217 SCREW - FAN MOTOR MOUNT CWH551040J PROPELLER FAN ASSY CWH001019 NUT - PROPELLER FAN CWH561038J...