Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
Substation 2 Substation 3 Substation N IEC140000114-2-en.vsd for the RES670, or via the IRIG-B signal received from an IEC140000114 V2 EN-US external GPS-based clock. It is also possible to have a Figure 1. Wide Area Monitoring System architecture — overview combination of the three to provide time synchronization redundancy for the PMU.
Page 4
Measuring functions for S, P, Q, I, U, PF, f are available for bays. RES670 A20 is delivered in 1/2, 3/4 and full (1/1)19" local presentation on the local HMI and remote presentation rack casing.
Page 5
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 RES670 A20 – Phasor Measurement Unit, 3 bays, single busbar, 12AI (9I+3U) WA1_VT df/dt SA PFRC f> SA PTOF f< SA PTUF 2(3U<) UV2 PTUV 2(3U>) OV2 PTOV...
Page 6
IEEE C37.118/1344. RES670 B20 is delivered in ¾, and full (1/1)19" rack casing. For this application 24 analog inputs are used, thus two In addition to the binary reporting channels there are 4 trigger...
Page 7
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 RES670 B20 – Phasor Measurement Unit, 6 bays, double busbar, 24AI (9I+3U, 9I+3U) WA1_VT WA2_VT df/dt df/dt SA PFRC SA PFRC f> f> SA PTOF SA PTOF f<...
Page 8
All been connected in the special way. On request, ABB is parameters should be verified by the customer, since these available to support the re-configuration work, either directly are specific to the system, object or application.
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 are not exposed to the user or do not need 2. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 to be configured are not described in this manual. The following tables list all the functions available in the IED.
Page 10
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Impedance protection ZMRPSB Power swing detection 1-B23 1-B23 OOSPPAM Out-of-step protection...
Page 11
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v16 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Control QCBAY Bay control LOCREM Handling of LR-switch positions...
Page 12
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) WRNCALH Logic for group warning INDCALH Logic for group indication AND, GATE, INV, Basic configurable logic blocks (see 40-420 40–420...
Page 13
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 1. Total number of instances for basic configurable logic blocks Basic configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SRMEMORY TIMERSET Table 2. Total number of instances for configurable logic blocks Q/T...
Page 14
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 3. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC...
Page 15
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement...
Page 16
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Metering PCFCNT Pulse-counter logic ETPMMTR Function for energy calculation and demand handling...
Page 17
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v16 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON DNPGEN DNP3.0 communication general protocol...
Page 18
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Phasor measurement unit function name RES670 (Customized) RCHLCCH Access point diagnostic for redundant Ethernet ports QUALEXP IEC 61850 quality expander Remote communication...
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 5. Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5...
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 synchrophasor frame format. The PMUREPORT block EF4PTOC has an inverse or definite time delay independent contains parameters for PMU performance class and for each step. reporting rate, the IDCODE and Global PMU ID, format of the...
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 for operating quantity with maintained short circuit capacity. It has a high reset ratio to allow settings close to the system There is also available one nondirectional 3I0 step and one service voltage.
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 9. General calculation Rate-of-change of frequency protection SAPFRC M14965-3 v13 The rate-of-change of frequency protection function Multipurpose filter SMAIHPAC GUID-EB0B11C3-FF79-4B8D-A335-649623E832F9 v3 (SAPFRC ) gives an early indication of a main disturbance in The multi-purpose filter function block (SMAIHPAC) is the system.
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 11. Control can be used for direct commands for example reset of LEDs or putting IED in "ChangeLock" state from remote. In this Circuit breaker SXCBR way, simple commands can be sent directly to the IED...
Page 24
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 according to the specific application needs for settable pulse • SRMEMORY function block is a flip-flop that can set or or steady output. reset an output from two inputs respectively. Each block has two outputs where one is inverted.
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 • PULSETIMERQT Pulse timer function block can be used, • Retaining of the integration value. for example, for pulse extensions or limiting of operation • Possibilities for blocking and reset.
Page 26
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 The event list logs all binary input signals connected to the Supervision of mA input signals Disturbance recorder function. The list may contain up to M16054-3 v2 The main purpose of the function is to measure and process 1000 time-tagged events stored in a ring-buffer.
Page 27
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 actions) and long perspective (for example functional Insulation supervision for gas medium function SSIMG analysis). GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6 Insulation supervision for gas medium (SSIMG) is used for monitoring the circuit breaker condition. Binary information...
RSTDMD input. Time synchronization M11344-3 v11 The time synchronization source selector is used to select a common source of absolute time for the IED. For RES670 as 15. Human machine interface a Phasor Measurement Unit (PMU) an accurate time Local HMI...
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Only GPS and IRIG-B (Optical IRIG-B 00X is recommended), IEC 62439-3 High-availability seamless redundancy HSR with IEEE1344 support, are the acceptable time Redundant station bus communication according to IEC...
Page 30
I103SUPERV is a function block with defined functions for SPA communication protocol SEMOD120134-5 v1 supervision indications in monitor direction. This block A single glass or plastic port is provided for the ABB SPA includes the FunctionType parameter; the information number protocol. This allows extensions of simple substation parameter is defined for each output signal.
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 19. Remote communication IED commands for IEC 60870-5-103 I103IEDCMD I103IEDCMD is a command block in control direction with Analog and binary signal transfer to remote end M12449-6 v3 defined IED functions.
Page 32
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Binary output module BOM Alternative connectors of Ring lug or Compression type can M6938-3 v4 The binary output module has 24 independent output relays be ordered. and is used for trip output or any signaling purpose.
Page 33
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M15243-12 v9 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 9. A 1/2 x 19” size IED side-by-side with RHGS6. Case size (mm)/(inches) 6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/...
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 21. Connection diagrams Connection diagrams for Configured products GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v7 The connection diagrams are delivered in the IED Connectivity Connection diagram, RES670 2.2, A20X00 1MRK002807-SA package as part of the product delivery.
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 22. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range...
Page 36
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 6. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency...
Page 37
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 7. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
Page 38
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Binary inputs and outputs M12576-1 v11 IP15844-1 v1 Table 10. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20%...
Page 39
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Maximum 176 binary input channels may The stated operate time for functions be activated simultaneously with influencing include the operating time for the binary factors within nominal range.
Page 40
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Maximum 176 binary input channels may The stated operate time for functions be activated simultaneously with influencing include the operating time for the binary factors within nominal range.
Page 41
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M12584-1 v9 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 14. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Page 42
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 SEMOD175395-2 v8 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 15. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs...
Page 43
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M12441-1 v9 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 17. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Page 44
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 19. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/%...
Page 45
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 21. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
Page 46
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 23. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
Page 47
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Impedance protection M16036-1 v10 Table 26. Power swing detection ZMRPSB Function Range or value Accuracy Reactive reach (0.10-3000.00) W/phase ±2.0% static accuracy Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I...
Page 48
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 standard), the compliancy to the standard is limited to the Wide area measurement system current range between 50% and 200% of rated current for GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v4 The IED is compliant with the synchrophasor measurement both P and M classes of the standard.
Page 49
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Current protection M12342-1 v21 Table 28. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy lBase Operate current, step 1-4 (5-2500)% of ±1.0% of I at I ≤...
Page 50
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M15223-1 v17 Table 29. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
Page 51
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 30. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I £...
Page 52
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 SEMOD173350-2 v16 Table 31. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional residual ±1.0% of I at I £...
Page 53
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M12352-1 v15 Table 32. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F...
Page 54
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 SEMOD175159-2 v9 Table 34. Directional overpower protection GOPPDOP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
Page 55
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Voltage protection M13290-1 v15 Table 35. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of...
Page 56
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M13304-1 v14 Table 36. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
Page 57
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Frequency protection M13360-1 v15 Table 37. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f...
Page 58
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M14976-1 v10 Table 39. Rate-of-change of frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz...
Page 59
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Multipurpose protection M13095-2 v10...
Page 60
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 41. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-phase3, phase3-phase1,...
Page 61
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 41. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater 0.8 x U...
Page 62
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 41. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x...
Page 63
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Secondary system supervision M12358-1 v10 Table 42. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I >...
Page 64
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Control...
Page 65
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Scheme communication...
Page 66
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Logic M12380-1 v13 Table 44. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
Page 67
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3 Table 51. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3 Table 52. Number of GATE instances...
Page 68
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-C6C98FE0-F559-45EE-B853-464516775417 v3 Table 59. Number of TIMERSET instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSET (0.000–90000.000) s ±0.5% ±10 ms GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2 Table 60.
Page 69
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1 Table 67. Number of PULSETIMERQT instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms (0.000–90000.000) s ±0.5% ±10 ms...
Page 70
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v7 Table 72. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms 8 ms 100 ms SLGAPC VSGAPC PULSETIMER GATE —...
Page 71
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4 Table 77. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC Function Cycle time (ms) Range or value Accuracy Elapsed time integration 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is...
Page 72
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Monitoring M12386-1 v16 Table 81. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U>...
Page 73
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 84. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V...
Page 74
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M12760-1 v11 Table 88. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings...
Page 75
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8 Table 90. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value...
Page 76
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 M12702-1 v4 Table 94. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time...
Page 77
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Metering M13404-2 v5 Table 99. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value SEMOD153707-2 v5 Table 100.
Page 78
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Station communication M15031-1 v9 Table 101. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
Page 79
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 105. SFP - Galvanic RJ45 Quantity Rated value Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for...
Page 80
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Hardware M11778-1 v7 SEMOD53385-1 v1 Table 107. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v5 Table 108.
Page 81
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 connections, one blank slot is necessary between two adjacent IO modules. Please refer to the ordering particulars for details. Table 113. NUM: Communication ports 4 Ethernet ports...
Page 82
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Basic IED functions M11963-1 v5 Table 115. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 116.
Page 83
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 SEMOD141136-2 v9 Table 120. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
Page 84
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Inverse characteristic M12388-1 v23 Table 121. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤...
Page 85
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 122. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is...
Page 86
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 123. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤...
Page 87
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 125. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I...
Page 88
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 SEMOD116978-2 v10 Table 127. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
Page 89
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 128. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
Page 90
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 129. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01...
The selected qty of each table must be filled in, if no selection is possible the code is 0 Example of a complete code: RES670*2.2-F00X00 - A000000000000000 - B00000000000000000100020000 - C06000666660000004400000000 - D22000000 - E66600 - F6 - S0 - G220 - H00000000000 - K00000000 - L1100 - M1800 - P01110011001100000 - B1X0 - AC - CA - B - A3X0 - CD1AN1 - KKKXXHKKSXXXX...
Page 92
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 135. Impedance protection Position Table 136. Impedance functions Function Function Ordering no Position Available Selected Notes and rules identification Power swing detection ZMRPSB 1MRK005907-UA 0–1 Out-of-step protection...
Page 93
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 144. Multipurpose functions Function Function Ordering no Position Available Selected Notes and rules identification General current and voltage protection CVGAPC 1MRK005915-AA 0–8 Table 145. General calculation Position Table 146.
Page 94
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 156. Station communication functions Function Function identification Ordering no Position Available Selected Notes and rules IEC 61850-9-2 Process bus communication, 8 1MRK005933-HA 0–1 merging units IEC 62439-3 Parallel redundancy protocol 1MRK005932-FA 0–1...
Page 95
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 160. Power supply module selection Power supply module Ordering no Selection Notes and rules Compression terminals 1MRK002960-GA Ringlug terminals 1MRK002960-HA Power supply module 24-60 VDC 1MRK002239-AB Power supply module 90-250 VDC...
Page 96
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 163. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
Page 97
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 165. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █ █ █...
Page 98
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 165. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, 1MRK000173-BE 10+2 outputs, RL110, 110-125VDC, 50mA IOM 8 inputs,...
Page 99
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Table 166. Station communication and time synchronization selection Station communication and time Ordering no Selection Notes and rules synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 case █...
To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: RES670*2.2-A20-B23C18C26F01G01P16P23-B1X0-AA-CA-B-B3X0-CB1AXXXXXXXXXXXX-KXXXXHKKGSXXX. Using the code of each position #1-11 specified as RES670*1-2-3 3 3 3 3 3 3-4 4-5 6-7 7-8-9 9 9-10 10 10-11 11 11 11 11 11 11 RES670*...
Page 101
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Language Ordering no Notes and rules First local HMI user dialogue language HMI language, English IEC 1MRK002930-AA Additional local HMI user dialogue language No additional HMI language HMI language, English US...
Page 102
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Analog system Ordering no Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug).
Page 103
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1BIM and 1 BOM required in positions P3 and P4...
Page 104
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1BIM and 1 BOM required in positions P3 and P4...
Page 105
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Station communication and time Ordering no Notes and rules synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 case █ █ █ █ █...
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 25. Ordering for Accessories Accessories IP15151-1 v1 GPS antenna and mounting details M12374-3 v5 GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA Cable for antenna, 20 m (Appx. 65 ft)
Page 107
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 Configuration and monitoring tools M15042-3 v4 IP15162-1 v2 Front connection cable between LHMI and PC Quantity: 1MRK 001 665-CA SEMOD131414-4 v3 LED Label special paper A4, 1 pc...
Page 108
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 511 407-UEN ANSI Quantity: 1MRK 511 407-UUS Technical manual Quantity: 1MRK 511 408-UEN ANSI...
Page 109
1MRK 511 410-BEN B Phasor measurement unit RES670 2.2 Product version: 2.2 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data:...