TECHNICAL CHANGES Service ref. have been changed as follows. MXZ-4C36NAHZ MXZ-4C36NAHZ-U1 MXZ-5C42NAHZ MXZ-5C42NAHZ-U1 MXZ-8C48NAHZ MXZ-8C48NAHZ-U1 MXZ-8C48NA MXZ-8C48NA-U1 OCH573E...
SAFETY PRECAUTION 1-1. ALWAYS OBSERVE FOR SAFETY Before obtaining access to terminal, all supply circuit must be disconnected. 1-2. CAUTIONS RELATED TO NEW REFRIGERANT Cautions for units utilizing refrigerant R410A Use a vacuum pump with a reverse flow check Use new refrigerant pipes. valve.
Page 4
[1] Cautions for service (1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) If moisture or foreign matter might have entered the refrigerant piping during service, ensure to remove them. [2] Additional refrigerant charge When charging directly from cylinder Unit...
OVERVIEW OF UNITS 2-1. CONSTRUCTION OF SYSTEM Capacity Models other than MXZ-8C60NA MXZ-8C60NA OCH573E...
Page 7
2-2. SYSTEM OUTLINE 2-2-1. System example Indoor unit (Ceiling concealed type) Indoor unit (Wall mounted type) Outdoor unit Branch box 2-2-2. Method for identifying Number of connectable indoor units (MAX.) Development No. : A, B, ···,etc. H Z - U1 M X Z - Sub-number Control and refrigerant...
Page 8
2-3. TYPICAL COMBINATION EXAMPLE Branch box is located INSIDE of condominium Branch box (Inside) Installing branch box indoors Branch box (5-branches type) Master Dining Bedroom (1) Bedroom (2) Living bedroom Outdoor unit SEZ-18 MSZ-12 MSZ-12 MSZ-09 MSZ-09 Example: SEZ-18 = 18 MSZ-12 = 12 Total rated capacity...
Page 9
2-4. SIMPLIFIED PIPING SYSTEM Piping connection size The piping connection size differs according to the type and capacity of indoor units. {3/8 inch Liquid Match the piping connection size of branch box with indoor unit. [9.52 mm] If the piping connection size of branch box does not match the piping connection size of {5/8 inch {3/4 inch* indoor unit, use optional different-diameter (deformed) joints to the branch box side.
SPECIFICATIONS kcal/h = kW o 860 3-1. OUTDOOR UNIT: Conversion formula: BTU/h = kW o 3412 MXZ-4C36/5C42/8C48NAHZ(-U1), MXZ-8C48NA(-U1), MXZ-8C60NA-U1 /min o 35.31 Service Ref. MXZ-4C36NAHZ(-U1) MXZ-5C42NAHZ(-U1) OCH573E...
Page 11
kcal/h = kW o 860 Conversion formula: BTU/h = kW o 3412 /min o 35.31 Service Ref. MXZ-8C48NAHZ(-U1) MXZ-8C48NA(-U1) OCH573E...
Page 12
kcal/h = kW o 860 BTU/h = kW o 3412 Conversion formula: /min o 35.31 Service Ref. MXZ-8C60NA-U1 OCH573E...
Page 13
3-2. BRANCH BOX: PAC-MKA50BC PAC-MKA51BC PAC-MKA30BC PAC-MKA31BC PAC-MKA50BC PAC-MKA30BC Model name PAC-MKA51BC PAC-MKA31BC Connectable number of indoor units Maximum 5 Maximum 3 Power supply Single phase, 208/230 V, 60 Hz Input 0.003 Running current 0.05 External finish Galvanized sheets inch (mm) 17-23/32 (450) Width Dimensions...
DATA 4-1. SELECTION OF COOLING/HEATING UNITS How to determine the capacity when less than or equal 100% indoor model size units are connected in total: The purpose of this flow chart is to select the indoor and outdoor units. For other purposes, this flow chart is intended only for reference. Determine the load (L) and the Indoor/Outdoor Temperature Temporarily select the Indoor/Outdoor Units...
Page 15
How to determine the capacity when greater than 100% indoor model size units are connected in total: for reference. Determine the load (L) and the Indoor/Outdoor Temperature Temporarily select the indoor/outdoor units Reselect the indoor units Reselect the indoor units Reselect the outdoor units Reselect the outdoor units Indoor Unit...
Page 16
<Cooling> Design Condition Outdoor Design Dry Bulb Temperature 98.6ºF (37.0ºC) Total Cooling Load 29.6 kBTU/h Room1 Indoor Design Dry Bulb Temperature 80.6ºF (27.0ºC) Indoor Design Wet Bulb Temperature 68.0ºF (20.0ºC) Cooling Load 13.6 kBTU/h Room2 Indoor Design Dry Bulb Temperature 75.2ºF (24.0ºC) Indoor Design Wet Bulb Temperature 66.2ºF (19.0ºC)
Page 17
<Heating> Design Condition Outdoor Design Wet Bulb Temperature 35.6ºF (2.0ºC) Total Heating Load 34.4 kBTU/h Room1 Indoor Design Dry Bulb Temperature 69.8ºF (21.0ºC) Heating Load 16.3 kBTU/h Room2 Indoor Design Dry Bulb Temperature 73.4ºF (23.0ºC) Heating Load 18.1 kBTU/h <Other> Indoor/Outdoor Equivalent Piping Length 230 ft Capacity of indoor unit 2.
Page 18
3. Power input of outdoor unit Outdoor unit : MXZ-4C36 Indoor unit 1 : MSZ-FH15 Indoor unit 2 : MSZ-FH18 <Cooling> (1) Rated power input of outdoor unit 2.57 kW (2) Calculation of the average indoor temperature power input coefficient Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp.
Page 19
<Heating> (1) Rated power input of outdoor unit 3.34 kW (2) Calculation of the average indoor temperature power input coefficient Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp. 26.6°F [ 3°C] W.B., Indoor temp. 68.0°F [20°C] D.B.) 1.34 (Refer to “4-2.
4-3. STANDARD OPERATION DATA (REFERENCE DATA) Operation Indoor Ambient DB/WB temperature Outdoor No. of connected units Unit Indoor unit No. of units in operation Model — Operating Main pipe conditions Piping Branch pipe Total pipe length Fan speed — lb oz Amount of refrigerant (kg) Electric current...
4-4. STANDARD CAPACITY DIAGRAM 4-4-1. MXZ-4C36NAHZ <cooling> Total capacity of indoor units (kBTU/h) Total capacity of indoor units (kBTU/h) 208, 230 V Total capacity of indoor units (kBTU/h) OCH573E...
4-4-2. MXZ-4C36NAHZ <heating> Total capacity of indoor units (kBTU/h) Total capacity of indoor units (kBTU/h) 208, 230 V Total capacity of indoor units (kBTU/h) OCH573E...
4-4-3. MXZ-5C42NAHZ <cooling> Total capacity of indoor units (kBTU/h) Total capacity of indoor units (kBTU/h) 208, 230 V Total capacity of indoor units (kBTU/h) OCH573E...
4-4-4. MXZ-5C42NAHZ <heating> Total capacity of indoor units (kBTU/h) 15.0 22.5 30.0 37.5 45.0 52.5 60.0 Total capacity of indoor units (kBTU/h) 208, 230 V 60.0 15.0 22.5 30.0 37.5 45.0 52.5 Total capacity of indoor units (kBTU/h) OCH573E...
4-4-5. MXZ-8C48NA MXZ-8C48NAHZ <cooling> Total capacity of indoor units (kBTU/h) Total capacity of indoor units (kBTU/h) 208, 230 V Total capacity of indoor units (kBTU/h) OCH573E...
4-4-6. MXZ-8C48NA MXZ-8C48NAHZ <heating> Total capacity of indoor units (kBTU/h) Total capacity of indoor units (kBTU/h) 208, 230 V Total capacity of indoor units (kBTU/h) OCH573E...
5-2. BRANCH BOX Unit: mm <inch> PAC-MKA50BC PAC-MKA51BC When installing the conduit. Set the attachment to the inner side of each panel. 58 〈2-9/32〉 SUSPENSION BOLT PITCH 320〈12-19/32〉 〈25/32〉 〈1-3/32〉 SUSPENSION BOLT : W3/8(M10) REFRIGERANT PIPE FLARED CONNECTION Unit: inch TO OUTDOOR UNIT LIQUID PIPE 1/4F...
7-2. REFRIGERANT SYSTEM DIAGRAM MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ MXZ-4C36NAHZ-U1 MXZ-5C42NAHZ-U1 MXZ-8C48NAHZ-U1 Thermistor(TH-A–E) Thermistor(TH7) <Gas pipe temperature> Service port <Ambient> Service port 4-Way Valve (21S4) Strainer Room temperature Ball valve High pressure thermistor Oil separator switch(63H) Solenoid valve(SV1) (TH1 or RT11) <Bypass>...
MXZ-8C60NA-U1 Thermistor(TH-A–E) Thermistor(TH7) <Gas pipe temperature> Service port <Ambient> Service port 4-Way Valve (21S4) Strainer Room temperature Ball valve High pressure thermistor Oil separator switch(63H) Solenoid valve(SV1) (TH1 or RT11) <Bypass> Strainer Capillary Distributor tube1 Service port Strainer Thermistor(TH3) High <Outdoor Liquid pipe>...
7-3. TYPICAL CONTROL SYSTEM IMPORTANT: TB3A TB5/TB15 Branch Box A-IC If a current leakage breaker is used, it should be compatible with higher MA-RC (01) (51) harmonics as this unit is equipped with an inverter. The use of an inadequate TB3B TB5/TB15 breaker can cause the incorrect operation of inverter.
Page 51
( 5) Group setting (6) Restricted functions OCH573E...
TROUBLESHOOTING 8-1. TROUBLESHOOTING <Check code displayed by self-diagnosis and actions to be taken for service (summary)> Unit conditions at service Check code Actions to be taken for service (summary) Judge what is wrong and take a corrective action according Displayed to “8-3 SELF-DIAGNOSIS ACTION BY FLOWCHART”.
Page 53
8-2. CHECK POINTS FOR TEST RUN 8-2-1. Procedures before test run " " OCH573E...
Page 54
8-2-2. Test run for wired remote controller <PAR-31MAA> MENU RETURN SELECT ON/OFF Function buttons Select "Service" from the Main menu, and press the button. Test run Input maintenance info. Function setting Check Self check Select "Test run" with the button, and press the button.
Page 55
8-2-3. Test run About the restart protective mechanism OCH573E...
In case of the test run from outdoor unit, all indoor units operate. Therefore, you cannot detect any erroneous con- nection of refrigerant pipes and the connecting wires. If it aims at detection of any erroneous connection, be sure to carry out the test run from remote controller with reference to "(1) Using remote controller." SW3-1 Cooling operation SW3-2...
Page 57
8-2-4. Countermeasures for Error During Test Run Detected Unit Remote Indoor Outdoor Controller NOTES: 1. When the outdoor unit detects No ACK error/No response error, an object indoor unit is treated as a stop, and not assumed to be abnormal. 2.
Page 58
8-3. SELF-DIAGNOSIS ACTION BY FLOWCHART Check code Abnormal points and detection methods Causes and checkpoints Diagnosis Remedy OCH573E...
Page 59
Check code Abnormal points and detection methods Causes and checkpoints Diagnosis Remedy OCH573E...
Page 73
Check code Abnormal points and detection methods Causes and checkpoints Diagnosis Remedy Turn the power OFF to check for looseness, disconnection or converse phases of the compressor wiring OCH573E...
8-5. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR State (CN51) A Distant control board E Lamp power supply B Relay circuit F Procure locally C External output adapter (PAC-SA88HA-E) G Max. 10 m CN51 D Outdoor unit control board : Error display lamp : Compressor operation lamp X, Y: Relay (Coil standard of 0.9W or less for 12 V DC) X, Y: Relay (1mA DC)
Page 109
8-6. HOW TO CHECK THE PARTS OUTDOOR UNIT: MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ MXZ-8C48NA MXZ-4C36NAHZ-U1 MXZ-5C42NAHZ-U1 MXZ-8C48NAHZ-U1 MXZ-8C48NA-U1 MXZ-8C60NA-U1 Parts name Check points Thermistor (TH3) Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 50 to 80 F [10 to 30 :]) <Outdoor liquid pipe>...
Page 110
Check method of DC fan motor (fan motor/outdoor multi controller circuit board) Notes 1. High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service. 2. Do not pull out the connector (CNF1, 2) for the motor with the power supply on. board and fan motor.) (It causes trouble of the outdoor multi controller circuit Self check...
Page 111
Check method of multi controller circuit board Multi controller circuit board check Fuse check Check the fuse on multi controller circuit board Disconnect the FAN motor connector and Replace multi controller circuit board (MULTI. B.) Did the fuse (F500) blow? measure the resistance of connector pins.
Page 112
Check method of power circuit board Power circuit board check Note: To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited. Is the voltage of main incoming power Check the breaker and power supply.
Page 113
Check method of M-NET power circuit board M-NET power circuit board check * To check the voltage of the parts on this board with a tester is difficult due to its location. Test points are limited. Check the voltage between M1 and M2 on the transmission terminal block TB3.
Page 114
8-7. HOW TO CHECK THE COMPONENTS <Thermistor characteristic Graph> Low temperature thermistors " 4 14 32 50 68 86 104122 °F 20 10 0 10 20 30 40 50 Temperature Medium temperature thermistor " " " " " " 167 212 230 257 ºF 100 110 125 : High temperature thermistor "...
Page 115
<HIGH PRESSURE SENSOR> Comparing the High Pressure Sensor Measurement and Gauge Pressure By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the high pressure sensor appears on the LED1, 2 on the control board. The figure at left shows that the switches 1 through 4 are set to ON and 5 through 8 are set to OFF.
Page 116
<LOW PRESSURE SENSOR> Comparing the Low Pressure Sensor Measurement and Gauge Pressure By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the low pressure sensor appears on the LED1 on the control board. The figure at left shows that the switches 1 through 4 are set to ON and 5 through 8 are set to OFF.
Page 117
BRANCH BOX: PAC-MKA50BC PAC-MKA51BC PAC-MKA30BC PAC-MKA31BC Parts name Check points Disconnect the connector then measure the resistance with a tester. Thermistor (TH-A–E) (At the ambient temperature 50 to 86°F [10 to 30:]) <Gas pipe> Normal Abnormal 4.3 to 9.6k" Open or short Disconnect the connector then measure the resistance with a tester.
Page 118
(1) Operation summary of the linear expansion valve branch box controller board 12V DC Drive circuit Blue Orange Yellow White Connector LEV-A LEV-B LEV-C LEV-D LEV-E <Output pulse signal and the valve operation> Output Output (Phase) (2) Linear expansion valve operation Open Close Open...
Page 119
(3) How to attach and detach the coil of linear expansion valve Main body Coil Lead wire Stopper <How to detach the coil> <How to attach the coil> Be sure to attach the stopper to pipe B. OCH573E...
Troubleshooting Check point Corrective measure Problem Locked expansion Replace the linear If the linear expansion valve becomes locked and the motor is still operating, valve expansion valve. the motor will emit a clicking noise and will not function. This clicking noise indicates an abnormality.
Page 121
8-8. TEST POINT DIAGRAM Outdoor multi controller circuit board MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ MXZ-8C48NA MXZ-4C36NAHZ-U1 MXZ-5C42NAHZ-U1 MXZ-8C48NAHZ-U1 MXZ-8C48NA-U1 MXZ-8C60NA-U1 <CAUTION> TEST POINT 1 is high voltage. CN51 CN102 CN40,CN41 CNS2 SWU2, SWU1 CNS1 CNLVB CNLVA CN52 CN3N CN3D CNAC TH2 Thermistor...
Page 122
Brief Check of POWER MODULE Outdoor power circuit board MXZ-4C36NAHZ MXZ-5C42NAHZ MXZ-8C48NAHZ MXZ-8C48NA MXZ-4C36NAHZ-U1 MXZ-5C42NAHZ-U1 MXZ-8C48NAHZ-U1 MXZ-8C48NA-U1 MXZ-8C60NA-U1 CN52C CNDC E2, E3 Power module U/V/W DCL1, DCL2 EI, E4 CNAC2 CNAC1 NI, LI OCH573E...
Page 124
Branch box controller board PAC-MKA50BC PAC-MKA51BC PAC-MKA30BC PAC-MKA31BC TH-A to E LEV-A to E TH-D and E LEV-D and E CN3M LED1,LED2 SW12 SW11 F2,F3,F4 TB3A to E OCH573E...
Page 125
8-9. INTERNAL SWITCH FUNCTION TABLE (1) Function of switches MXZ-4C36NAHZ(-U1) MXZ-5C42NAHZ(-U1) MXZ-8C48NAHZ(-U1) MXZ-8C48NA(-U1) MXZ-8C60NA-U1 OCH573E...
Page 140
8-12. SELECTING FUNCTIONS USING THE REMOTE CONTROLLER : Initial setting Function Settings Mode No. Setting No. Remarks (when sent from the factory) Power failure automatic recovery The setting can Average data from each indoor unit be made to Indoor temperature each indoor Data from the indoor unit with remote controller detecting...
PRECAUTIONS AGAINST REFRIGERANT LEAKAGE 9-1. PRECAUTIONS AGAINST REFRIGERANT LEAKAGE 9-1-1. Introduction Outdoor unit Direction of refrigerant flow Branch box Indoor unit All refrigerant of this system will leak out to this room if there is leakage at this indoor unit. 9-1-2.
DISASSEMBLY PROCEDURE 10-1. OUTDOOR UNIT MXZ-4C36NAHZ(-U1) MXZ-5C42NAHZ(-U1) MXZ-8C48NAHZ(-U1) OPERATING PROCEDURE PHOTOS/FIGURES Removing the service panel and top panel Photo 1 2. Removing the fan motor (MF1, MF2) Photo 2 Photo 3 Note: Tighten the propeller fan with a torque of 5.7 ± 0.3 N·m.
Page 143
OPERATING PROCEDURE PHOTOS/FIGURES Photo 5 4. Removing the thermistor <Suction pipe> (TH6) Photo 6 Note: When replacing thermistor <Suction pipe> (TH6), replace it together with thermistor <Ambient> (TH7) since they are combined together. Refer to procedure No.5 below to remove thermis- tor <Ambient>...
Page 144
OPERATING PROCEDURE PHOTOS/FIGURES 6. Removing the thermistor <Outdoor liquid pipe> (TH3) and Photo 9 Photo 9 thermistor <Compressor> (TH4), thermistor <HIC pipe> (TH2) 7. Removing the 4-way valve coil (21S4) Photo 10 8. Removing the 4-way valve Notes: 1. Recover refrigerant without spreading it in the air. 2.
Page 145
OPERATING PROCEDURE PHOTOS/FIGURES 9. Removing bypass valve coil (SV1, SV2) and bypass valve Photo 11 Refer to the notes below. 10. Removing the high pressure switch (63H) and high pres- sure sensor (63HS) Refer to the notes below. 11. Removing the low pressure sensor (63LS) Photo 12 Refer to the notes below.
Page 146
OPERATING PROCEDURE PHOTOS/FIGURES 13. Removing the compressor (MC) Photo 13 Figure 2 Note: Recover refrigerant without spreading it in the air. 14. Removing the accumulator Photo 14 Note: Recover refrigerant without spreading it in the air. Photo 15 OCH573E...
Page 147
OPERATING PROCEDURE PHOTOS/FIGURES Figure 3 15. Removing the reactor (DCL) 16. Removing the base heater Photo 16 Notes: Photo 17 1. Tighten the propeller fan with a torque of 5.7 ± 0.3 N·m [4.2 ± 0.2 ft = lbs] 2. Rotate the propeller fan and make sure that the base heater and the lead wires do not interfere with the movement of the propeller fan.
Page 148
MXZ-8C48NA MXZ-8C48NA-U1 OPERATING PROCEDURE PHOTOS/FIGURES 1. Removing the service panel and top panel Figure 1 2. Removing the fan motor (MF1, MF2) Photo 1 Photo 2 Note: Tighten the propeller fan with a torque of 5.7 ± 0.3 N·m [4.2 ± 0.2 ft = lbs] 3.
Page 149
OPERATING PROCEDURE PHOTOS/FIGURES Photo 4 4. Removing the thermistor <Suction pipe> (TH6) Photo 5 Note: When replacing thermistor <Suction pipe> (TH6), replace it together with thermistor <Ambient> (TH7) since they are combined together. Refer to procedure No.5 below to remove thermis- tor <Ambient>...
Page 150
OPERATING PROCEDURE PHOTOS/FIGURES Photo 8 6. Removing the thermistor <Outdoor liquid pipe> (TH3) and thermistor <Compressor> (TH4), thermistor <HIC pipe> (TH2) 7. Removing the 4-way valve coil (21S4) Photo 9 8. Removing the 4-way valve Note: 1. Recover refrigerant without spreading it in the air. 2.
Page 151
OPERATING PROCEDURE PHOTOS/FIGURES Photo 10 9. Removing bypass valve coil (SV1) and bypass valve Refer to the notes below. 10. Removing the high pressure switch (63H) and high pres- sure sensor (63HS) Photo 11 Refer to the notes below. 11. Removing the low pressure sensor (63LS) Refer to the notes below.
Page 152
OPERATING PROCEDURE PHOTOS/FIGURES 13. Removing the compressor (MC) Photo 13 Figure 3 Note: Recover refrigerant without spreading it in the air. 14. Removing the accumulator Photo 14 Note: Recover refrigerant without spreading it in the air. Photo 15 OCH573E...
Page 154
MXZ-8C60NA-U1 OPERATING PROCEDURE PHOTOS/FIGURES 1. Removing the service panel and top panel Photo 1 2. Removing the fan motor (MF1, MF2) Photo 2 Photo 3 Note: Tighten the propeller fan with a torque of 5.7 ± 0.3 N·m [4.2 ± 0.2 ft = lbs] 3.
Page 155
OPERATING PROCEDURE PHOTOS/FIGURES Photo 5 4. Removing the thermistor <Suction pipe> (TH6) Photo 6 Note: When replacing thermistor <Suction pipe> (TH6), replace it together with thermistor <Ambient> (TH7) since they are combined together. Refer to procedure No.5 below to remove thermis- tor <Ambient>...
Page 156
OPERATING PROCEDURE PHOTOS/FIGURES Photo 9-1 6. Removing the thermistors Thermistor <HIC> (TH2) and thermistor <Compressor> (TH4) Thermistor <Outdoor pipe> (TH3) Photo 9-2 Photo 10 7. Removing the 4-way valve coil (21S4) [Removing the 4-way valve coil] 8. Removing the 4-way valve 1.
Page 157
OPERATING PROCEDURE PHOTOS/FIGURES Photo 11 9. Removing bypass valve coil (SV1) and bypass valve Refer to the notes below. 10. Removing the high pressure switch (63H) and high pres- sure sensor (63HS) Refer to the notes below. 11. Removing the low pressure sensor (63LS) Photo 12 Refer to the notes below.
Page 158
OPERATING PROCEDURE PHOTOS/FIGURES Figure 2 13. Removing the reactor (DCL) 14. Removing the compressor (MC) Photo 13 Note: Recover refrigerant without spreading it in the air. Figure 3 Photo 14 OCH573E...
Page 159
OPERATING PROCEDURE PHOTOS/FIGURES Photo 15 15. Removing the accumulator Note: Recover refrigerant without spreading it in the air. Photo 16 OCH573E...
Page 160
10-2. BRANCH BOX: PAC-MKA50BC PAC-MKA51BC PAC-MKA30BC PAC-MKA31BC PHOTO: PAC-MKA50/51BC OPERATING PROCEDURE PHOTOS/FIGURES 1. Removing the controller cover and under panel Photo 1 2. Removing the thermistor (TH-A–E*) Photo 2-1 Photo 2-3 Photo 2-2 OCH573E...
Page 161
OPERATING PROCEDURE PHOTOS/FIGURES 3. Removing the LEV coil (LEV-A–E*) Photo 3 4. Removing the controller board Photo 4 OCH573E...
Page 162
OPERATING PROCEDURE PHOTOS/FIGURES 5. Removing the LEV assy Photo 5-1 <Removing the header assy> <Disassembling the pipe box> Photo 5-2 <Pipe box cap only for PAC-MKA30/31BC> Photo 5-4 Photo 5-4 Photo 5-3 Photo 5-5 Photo 5-5 OCH573E...
Need help?
Do you have a question about the MXZ-4C36NAHZ and is the answer not in the manual?
Questions and answers