Instructions Electronic Units 42/68-821 EN EAS822, EBS852, EBS862 (Contrac) For the Control of Contrac Actuators of the PME, LME, RHD or RSD Series...
Device Identification 1.2.1 ID Label on the Base (for Hardware Description of the Base) Elektronik / Electronics Type: ..1.1 ID Labels for Electronics EAS 822 + EBS 852 B-Nr./No..The ID labels of the power electronics are located on top of the units.
Safety and Precautions - Use Contrac power electronics EAS 822, EBS 852, and EBS 862 for driving the Contrac actuators specified on the electronics ID label, only. - Prior to maintenance or repair works always disconnect the electronics from mains and secure the respective control actuator against reactive process forces.
The electronic unit is designed for rail-mounting in a special rack providing four mounting levels. Either four units (EAS822 and / or EBS852) or one unit (EBS862) can be installed on each level. It is also pos- sible to mix the units, as seen in figure 5. Do not transport the rack with the units installed; the total weight is too high.
Page 6
5.1.2 EBS 862 1 PG cable gland for mains connection 2 PG cable gland for motor connection 3 PG cable glands for signal connection 4 Cover screws 5 Hinge screws 6 Commissioning and service field (CSF) d0112rxa Fig. 2: On the electronics side, the power supply and the motor cable are connected via screw terminals, and the signal cables are connected via an internal plug and socket connection.
Design 5.2.1 Electronic units The aluminum cases of the units are mounted to four stay bolts on the mounting rails. The units are installed, electrically connected and operated from the front. 5.2.2 Mounting Rack The rack is an open steel profile rack. Regarding construction and dimensions it is similar to commer- cially available cabinets (e.
Possible Arrangement in the Mounting Rack EBS 862 EBS 862 EBS 862 EBS 862 Fig. 5: Mounting rack with EAS 822 / EBS 852, possible Fig. 6: Mounting rack with EBS 862, possible arrangement arrangement...
Technical Data Electronics Electronics EAS822 EBS852 EBS862 Protection class IP 20 ≤ 75% annual average, no condensation permitted Humidity Intake air temperature at 0 ..45° C mounting rack Mounting orientation Vertical, connections from bottom or right Varnish 2-component epoxy resin (RAL 9005, black) 2 …...
115 V 230 V 1.5 mm 2.5 mm 4 mm 6 mm 10 mm electronic unit EAS822 60 W 1.0 A 0.55 A PME120 60 W 1.8 A 0.90 A RHD250-10 75 W 2.2 A 1.1 A RHD500-10 60 W 3.4 A...
9.1.1 Pre-condition - Disconnection must be possible on mounting site. - All signal cables and the motor cable between actuator and electronics must be shielded at both ends. EAS822 / EBS852 sub distribution board ext. fuse mains mains connect shield at both ends AC 110...250 V...
EBS862 Fig. 8: Electrical connection of EBS862 Connecting the shield - remove approx. 2 cm of the cable sheath at the end (1) - open the shielding and put it over the 2 inner cable sheath - push the cable through the cable gland and fasten it the terminal (3) - make sure that the shielding is in contact with the terminal and the housing of the...
Signal input / output (Examples) (conventional analogue / binary control) Premises to switch the actuator into automatic mode (AUT): - digital inputs D1, D2, and D3 may not be activated via the configuration software (standard config- uration with default factory settings). - activate the AUT mode using the configuration software (standard configuration with default factory settings).
Leistungskabel Signal- kabel Abschirmung Abschirmung Trenn- steg Fig. 12: Cable guidance within the plug Fuses 9.7.1 EAS822 Type Location = 115 V = 230 V Series fuse external 16 A; slow-blow Mains fuse F1, in terminal box 6.3 A; slow-blow 3.15 A;...
Page 15
9.7.3 EBS862 Type Location = 230 V Series fuse external 35 A fuse 16 A thermal safety cutout Relay fuse for DO1, DO2, F2 ... F4; in terminal box 3 x 0.2 A; medium time-lag Brake fuse on board (power section) 0.315 A medium time-lag Intermediate circuit fuse power board...
10. Operating and Connecting Elements 10.1 EAS822 / EBS852 Power Commissioning and Service Field 100% (CSF) RESET RS 232 Signal Signal Signal Motor Terminal Mains (r00345x1) Fig. 16: Position of operating and connecting elements on EAS822 / EBS852...
Front Fig. 19: Cable arrangement and electronic unit installation in a mounting rack (top view) 11.1 Mains distribution max.16 mm 10 11 12 13 14 15 16 N L1 L2 L3 Fig. 20: Arrangement of mains cables...
13.Setup The actuator only requires the basic settings (adaptation to the operating range) in order to be operated with the standard or custumer specific configuration. Use the Local Control Panel (LCP) for these set- tings. Use the appropriate configuration software for more detailed parameter changes or diagnosis functions.
13.1.4Setting 13.1.4.1 “Setting” mode - Set electronics to “setting” mode by pressing both push buttons (3) simultaneously for approx. 5 seconds, until both LEDs (2 + 8) are flashing synchronously at approx. 4Hz. („setting mode“ is the standard electronic unit status after passing the final factory test) 13.1.4.2 Defining first position (0% or 100%) (Higher precision in 2nd position) - Move to desired position by pressing one of the push buttons (3).
14. Alarms / Failures 14.1 Definition 14.1.1 Alarms The actuator / electronic unit is exposed to critical conditions (e. g. high temperature) which currently do not affect the actuator, the electronic unit, the process or persons. The actuator functions are still available.
15. Troubleshooting This section mainly describes how to handle hardware errors. Refer to the configuration program’s on- line help for errors related to the software. Error Possible reason Measures to be taken Valve cannot be moved by actuator Malfunction of actuator or valve (e.g. Disconnect the actuator from the stuffing box tightened too much) valve.