Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
ABB is not liable for any such damages and/or losses.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1)..................21 LD0.EFIPTOC1 Non-directional earth-fault protection, instantaneous stage (1)...............22 LD0.FDEFLPDEF1 Directional earth-fault protection, low stage (1)..................22 LD0.FDEFLPDEF2 Directional earth-fault protection, low stage (2)..................22 LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1)..................23 Recloser Protection and Control RER615 Point List Manual...
Page 8
LD0.TRPPTRC1 Protection trip conditioning (1)......32 LD0.TRPPTRC2 Protection trip conditioning (2)......32 LD0.MAPGAPC1 Multipurpose analog protection function (1)....................32 LD0.MAPGAPC2 Multipurpose analog protection function (2)....................33 LD0.MAPGAPC3 Multipurpose analog protection function (3)....................33 LD0.MAPGAPC4 Multipurpose analog protection function (4)....................33 Recloser Protection and Control RER615 Point List Manual...
Page 9
LD0.XGGIO130 Physical I/O states (BIO card X130) ....50 LD0.XGGIO120 Physical I/O states (AIM card X120)....51 LD0.XGGIO110 Physical I/O states (BIO card X110)....51 LD0.XGGIO100 Physical I/O states (PSM card X100)....52 LD0.XAGGIO130 Physical I/O states (AIM card XA130)....53 Recloser Protection and Control RER615 Point List Manual...
Page 10
LD0.CMSTA1 Phase current demand values (1) .......66 CTRL.CBCSWI1 Circuit breaker operation counter (1) ....67 LD0.PEMMTR1 Three-phase energy measurements (1)....68 System diagnostic values............68 Control structure 1...............69 Control structure 2...............69 Control structure 3...............69 Control structure 4...............69 Recloser Protection and Control RER615 Point List Manual...
IED perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. Recloser Protection and Control RER615 Point List Manual...
ABB Website http://www.abb.com/relion. 1.3.2 Document revision history Document revision/date Product version History A/2013-09-17 First release B/2015-03-06 Content updated to correspond to the product version Download the latest documents from the ABB Website http://www.abb.com/substationautomation. Recloser Protection and Control RER615 Point List Manual...
The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. Recloser Protection and Control RER615 Point List Manual...
1 Wattmetric based earth-fault WPWDE2 Po> -> (2) 32N (2) protection, instance 2 Wattmetric based earth-fault WPWDE3 Po> -> (3) 32N (3) protection, instance 3 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Page 17
Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5) Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6) Fault locator, instance 1 SCEFRFLO1 FLOC (1) 21FL (1) Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Page 18
Sequence voltage measurement, U1, U2, U0 (B) VSMSQI2 V1, V2, V0 (B) (1) instance 2 Three-phase power and energy PEMMXU1 P, E (1) P, E (1) measurement, instance 1 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Wattmetric based earth-fault protection WPWDE 5)7)8) 5)7)8) Harmonics based earth-fault protection HAEFPTOC 5)8) 5)8) Negative-sequence overcurrent protection NSPTOC Phase discontinuity protection PDNSPTOC Residual overvoltage protection ROVPTOV 9)10) Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Page 22
Residual current measurement RESCMMXU Three-phase voltage measurement VMMXU 1(2) Sequence voltage measurement VSMSQI 1(2) Three-phase power and energy measurement PEMMXU Frequency measurement FMMXU Load profile LDPMSTA Other Table continues on next page Recloser Protection and Control RER615 Point List Manual...
The signal may have a defined label that is visible, for example, in the Application Configuration tool in PCM600. Description Short description of the signal. See the technical manual for more information. Value Meaning of the value states. Recloser Protection and Control RER615 Point List Manual...
IEC 61850 name SA name Description Values LD0.PHPTUV1 3138 196.02 .Str.general START General start 1=Start 3139 196.03 .mcd 3140 196.04 .Str.phsA phsA start 1=Start 3141 196.05 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
LD0.PHPTOV3 Phase overvoltage protection (3) BitA RegA IEC 61850 name SA name Description Values LD0.PHPTOV3 3108 194.04 .Str.general START General start 1=Start 3109 194.05 .mcd 3110 194.06 .Str.phsA phsA start 1=Start Table continues on next page Recloser Protection and Control RER615 Point List Manual...
LD0.VMHAI1 Voltage total demand distortion (1) Table 52: LD0.VMHAI1 Voltage total demand distortion (1) BitA RegA IEC 61850 name SA name Description Values LD0.VMHAI1 3318 207.06 .Alm.stVal ALARM 1=Alarm 3319 207.07 .mcd Recloser Protection and Control RER615 Point List Manual...
CTRL.ESSXSWI2 Earthing switch indication (2) BitA RegA IEC 61850 name SA name Description Values CTRL.ESSXSWI2 POSITION 2807 175.07 .Pos.stVal.Close Close bit 1=Close 2808 175.08 .Pos.stVal.Open Open bit 1=Open 2809 175.09 .Pos.stVal.Fault Fault bit 1=Pos(00/11) Recloser Protection and Control RER615 Point List Manual...
Reclose ready 1=Ready 3063 191.07 .mcd 3064 191.08 .ActRec.stVal ACTIVE Reclose active 1=Active 3065 191.09 .mcd 3066 191.10 .PrgDsr.stVal DISCR_INPRO Discr.time in progress 1=In progress 3067 191.11 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
LD0.SSCBR1 2848 178.00 .OpnAlm.stVal TRV_T_OP_ALM Opn travel time alarm 1=Alarm 2849 178.01 .ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm 2850 178.02 .SprChaAlm.stVal SPR_CHR_ALM Spring charge alarm 1=Alarm Table continues on next page Recloser Protection and Control RER615 Point List Manual...
1=Low voltage 3971 248.03 .mcd 3972 248.04 .VDeaPhsB.stVal U_B_BC_DEAD Low phsB or phsBC voltage 1=Low voltage 3973 248.05 .mcd 3974 248.06 .VDeaPhsC.stVal U_C_CA_DEAD Low phsC or phsCA voltage 1=Low voltage 3975 248.07 .mcd Recloser Protection and Control RER615 Point List Manual...
3608 225.08 .SPCS05.stVal Ouput state 5 0/1=Off/On 3609 225.09 .mcd 3610 225.10 .SPCS06.stVal Ouput state 6 0/1=Off/On 3611 225.11 .mcd 3612 225.12 .SPCS07.stVal Ouput state 7 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Ouput state 5 0/1=Off/On 3641 227.09 .mcd 3642 227.10 .SPCS06.stVal Ouput state 6 0/1=Off/On 3643 227.11 .mcd 3644 227.12 .SPCS07.stVal Ouput state 7 0/1=Off/On 3645 227.13 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
4090 255.10 .SPCS06.stVal Ouput state 6 0/1=Off/On 4091 255.11 .mcd 4092 255.12 .SPCS07.stVal Ouput state 7 0/1=Off/On 4093 255.13 .mcd 4094 255.14 .SPCS08.stVal Ouput state 8 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Ouput state 6 0/1=Off/On 4059 253.11 .mcd 4060 253.12 .SPCS07.stVal Ouput state 7 0/1=Off/On 4061 253.13 .mcd 4062 253.14 .SPCS08.stVal Ouput state 8 0/1=Off/On 4063 253.15 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
LD0.LEDGGIO1 Indication LED states OFF/ColorX These LED indication points interpret the case when an indication signal is wired to either the OK or ALARM input of the LED function block. The default color for Recloser Protection and Control RER615 Point List Manual...
OK and ALARM inputs, but inverted to the other. This means that the LED toggles between red and green colors. The default color for ALARM is red and green for OK. Colors can, however, be reconfigured with a setting parameter. Recloser Protection and Control RER615 Point List Manual...
Page 55
0/1=Color1/2 3527 220.07 .ISCSO8.stVal LED 8 state 0/1=Color1/2 3528 220.08 .ISCSO9.stVal LED 9 state 0/1=Color1/2 3529 220.09 .ISCSO10.stVal LED 10 state 0/1=Color1/2 3530 220.10 .ISCSO11.stVal LED 11 state 0/1=Color1/2 3531 220.11 <reserved> Recloser Protection and Control RER615 Point List Manual...
BitA RegA IEC 61850 name SA name Description Values LD0.XGGIO130 3184 199.00 .Ind1.stVal X130-Input 1 State 0/1=Off/On 3185 199.01 .mcd 3186 199.02 .Ind2.stVal X130-Input 2 State 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
IEC 61850 name SA name Description Values LD0.XGGIO110 3216 201.00 .Ind1.stVal X110-Input 1 State 0/1=Off/On 3217 201.01 .mcd 3218 201.02 .Ind2.stVal X110-Input 2 State 0/1=Off/On 3219 201.03 .mcd Table continues on next page Recloser Protection and Control RER615 Point List Manual...
User definable registers [Alt.1], visible on 3x and 4x RegA Type Scale IEC 61850 name SA name Description Values < not mappable- not visible > User Register 1 User Register 2 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
< reserved > 130.03 < reserved > 130.04 Any momentary bit updated 1=Updated 130.05 Any mcd bit set 1=Set 130.06 Device restart bit 1=IED restart 130.07 < reserved > Table continues on next page Recloser Protection and Control RER615 Point List Manual...
SSR5 System status register (5) device alive register Table 98: SSR5 System status register (5) device alive register RegA Type Scale IEC 61850 name SA name Description Values Device alive counter 0...65535 Recloser Protection and Control RER615 Point List Manual...
Object temperature 9999.9 [C] 0.00…99.99 .TmpRl.mag TEMP_RL Relative temperature -99…999.99 .TmpUsed.mag TEMP_AMB Ambient temperature 0…600,000 .001 .TmmsOp.stVal THERMLEV_ST Est. time to operate [ms] 0…600,000 .001 .TmmsRecEna.stVal THERMLEV_END Est. time to deactivate block [ms] Recloser Protection and Control RER615 Point List Manual...
Scale IEC 61850 name SA name Description Values LD0.DARREC1 .AutoRecSt.stVal STATUS AR state -2...4 .ShotPntr.stVal SHOT_PTR AR shot pointer value 0...6 .OpCntRs.stVal COUNTER AR operation counter 0...65535 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
LD0.RESCMMXU1 Residual current measurement (1) Table 111: LD0.RESCMMXU1 Residual current measurement (1) RegA Type Scale IEC 61850 name SA name Description Values LD0.RESCMMXU1 Residual current (1) 0.00...40.0 1000 .A.res.instCVal.mag I0_INST - amplitude [xIn] Recloser Protection and Control RER615 Point List Manual...
(low word) .TotVAr.instMag Q_INST Total reactive power Q (high) -/+ 999,999 .TotVAr.instMag (low word) .TotVA.instMag S_INST Total apparent power S (high) -/+ 999,999 .TotVA.instMag (low word) 1000 .TotPF.instMag PF_INST Average power factor -1...1 Recloser Protection and Control RER615 Point List Manual...
0...4.0 [xUn] Update time stamp 1960 - Year - month 1961 - Day - hour 1962 - Minute - second 1963 - Milliseconds 1964 - Time quality 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
- phsC amplitude [xIn] Update time stamp 2004 - Year - month 2005 - Day - hour 2006 - Minute - second 2007 - Milliseconds 2008 - Time quality Table continues on next page Recloser Protection and Control RER615 Point List Manual...
CTRL.CBCSWI1 Circuit breaker operation counter (1) Table 124: CTRL.CBCSWI1 Circuit breaker operation counter (1) RegA Type Scale IEC 61850 name SA name Description Values CTRL.CBCSWI1 2027 .OpCntRs.stVal Operation counter Operation counter 0…65535 Recloser Protection and Control RER615 Point List Manual...
.NumPwrUp.stVal Num of cold starts 0...65535 2055 .WrmStr.stVal Num of warm starts 0...65535 2056 .WacTrg.stVal Num of watchdog resets 0...65535 2057 .NumCmpChg.stVal Num of conf. changes 0...65535 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
Values 8016 Execute register 8017 Password reg 1 acc to setting 8018 Password reg 2 acc to setting 8019 Control register < single bit > 8020 Confirm register < single bit > Recloser Protection and Control RER615 Point List Manual...
Values 8036 Execute register 8037 Password reg 1 acc to setting 8038 Password reg 2 acc to setting 8039 Control register < single bit > 8040 Confirm register < single bit > Recloser Protection and Control RER615 Point List Manual...
SA name Description Values 9211 Control register 0...2 9212 Year 2000...2999 9213 Month 1...12 9214 1...31 9215 Hour 0...23 9216 Minute 0...59 9217 Second 0...59 9218 Millisecond 0…999 1) See the technical manual. Recloser Protection and Control RER615 Point List Manual...
Timestamp of record 9254 - Year, Month Year/Month 9255 - Day, Hour Day/Hour 9256 - Minute, Second Min/Sec 9257 - Millisecond Millisecond 9258 Event identification 9259 Data object ID1 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Page 79
- Record sequence num 1...9999 9286 - Unread records left 0...499 Timestamp of record 9287 - Year, Month Year/Month 9288 - Day, Hour Day/Hour 9289 - Minute, Second Min/Sec Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Page 80
9317 Event data value 2 Record 7 data to read: If selected 9318 - Record sequence num 1...9999 9319 - Unread records left 0...499 Timestamp of record Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Page 81
- Minute, Second Min/Sec 9345 - Millisecond Millisecond 9346 Event identification 9347 Data object ID1 9348 Data object ID2 9349 Event data value 1 9350 Event data value 2 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
1000 .VoltsBb.mag PhsBb voltage 0...4.00 [xUn] 9445 1000 .VoltsCb.mag PhsCb voltage 0...4.00 [xUn] 9446 1000 .VoltsABb.mag PhsABb voltage 0...4.00 [xUn] 9447 1000 .VoltsBCb.mag PhsBCb voltage 0...4.00 [xUn] Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Values LD0.LLN0 2060 2.00 .LEDRs1.Oper.ctlVal Reset indications and LEDs 1=Reset 2061 2.01 .LEDRs2.Oper.ctlVal Reset Alarm LEDs 1=Reset LD0.PEMSTA1 2062 2.02 .RecRs.Oper.ctlVal Reset Power max demands 1=Reset LD0.DARREC1 Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Select open 1=Select 2049 1.01 .Pos.Oper.ctlVal Select close 1=Select 2050 1.02 .Pos.Oper.ctlVal Cancel selection 1=Cancel 2051 1.03 .Pos.Oper.ctlVal Execute selection 1=Execute 2052 1.04 .Pos.Oper.ctlVal Direct open 1=Open 2053 1.05 .Pos.Oper.ctlVal Direct close 1=Close Recloser Protection and Control RER615 Point List Manual...
IEC 61850 name SA name Description Values LD0.SPCGGIO1 2112 5.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On 2113 5.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On 2114 5.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On Table continues on next page Recloser Protection and Control RER615 Point List Manual...
Output 12 control 0/1=Off/On 2140 6.12 .SPCS13.ctlVal Output 13 control 0/1=Off/On 2141 6.13 .SPCS14.ctlVal Output 14 control 0/1=Off/On 2142 6.14 .SPCS15.ctlVal Output 15 control 0/1=Off/On 2143 6.15 .SPCS16.ctlVal Output 16 control 0/1=Off/On Recloser Protection and Control RER615 Point List Manual...
Output 11 control 0/1=Off/On 2427 .SPCS12.ctlVal Output 12 control 0/1=Off/On 2428 .SPCS13.ctlVal Output 13 control 0/1=Off/On 2429 .SPCS14.ctlVal Output 14 control 0/1=Off/On 2430 .SPCS15.ctlVal Output 15 control 0/1=Off/On 2431 .SPCS16.ctlVal Output 16 control 0/1=Off/On Recloser Protection and Control RER615 Point List Manual...
LHMI Local human-machine interface Modbus A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. Overcurrent PCM600 Protection and Control IED Manager Recloser Protection and Control RER615 Point List Manual...
Page 92
Contact us ABB Oy Medium Voltage Products, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...